™
FieldPoint FP-1000 and
FP-1001 RS-232/RS-485
Network Module
User Manual
FieldPoint FP-1000/FP-1001 User Manual
July 1997 Edition
Part Number 321631A-01
© Copyright 1997 National Instruments Corporation. All rights reserved.
Important Information
Warranty
The FieldPoint modules are warranted against defects in materials and workmanship for a period of one year from the
date of shipment, as evidenced by receipts or other documentation. National Instruments will, at its option, repair or
replace equipment that proves to be defective during the warranty period. This warranty includes parts and labor.
The media on which you receive National Instruments software are warranted not to fail to execute programming
instructions, due to defects in materials and workmanship, for a period of 90 days from date of shipment, as evidenced
by receipts or other documentation. National Instruments will, at its option, repair or replace software media that do
not execute programming instructions if National Instruments receives notice of such defects during the warranty
period. National Instruments does not warrant that the operation of the software shall be uninterrupted or error free.
A Return Material Authorization (RMA) number must be obtained from the factory and clearly marked on the outside
of the package before any equipment will be accepted for warranty work. National Instruments will pay the shipping
costs of returning to the owner parts which are covered by warranty.
National Instruments believes that the information in this manual is accurate. The document has been carefully
reviewed for technical accuracy. In the event that technical or typographical errors exist, National Instruments reserves
the right to make changes to subsequent editions of this document without prior notice to holders of this edition. The
reader should consult National Instruments if errors are suspected. In no event shall National Instruments be liable for
any damages arising out of or related to this document or the information contained in it.
EXCEPT AS SPECIFIED HEREIN, NATIONAL INSTRUMENTS MAKES NO WARRANTIES, EXPRESS OR IMPLIED, AND
SPECIFICALLY DISCLAIMS ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
CUSTOMER’S RIGHT TO RECOVER DAMAGES CAUSED BY FAULT OR NEGLIGENCE ON THE PART OF NATIONAL
INSTRUMENTS SHALL BE LIMITED TO THE AMOUNT THERETOFORE PAID BY THE CUSTOMER. NATIONAL INSTRUMENTS
WILL NOT BE LIABLE FOR DAMAGES RESULTING FROM LOSS OF DATA, PROFITS, USE OF PRODUCTS, OR INCIDENTAL OR
CONSEQUENTIAL DAMAGES, EVEN IF ADVISED OF THE POSSIBILITY THEREOF. This limitation of the liability of National
Instruments will apply regardless of the form of action, whether in contract or tort, including negligence. Any action
against National Instruments must be brought within one year after the cause of action accrues. National Instruments
shall not be liable for any delay in performance due to causes beyond its reasonable control. The warranty provided
herein does not cover damages, defects, malfunctions, or service failures caused by owner’s failure to follow the
National Instruments installation, operation, or maintenance instructions; owner’s modification of the product;
owner’s abuse, misuse, or negligent acts; and power failure or surges, fire, flood, accident, actions of third parties, or
other events outside reasonable control.
Copyright
Under the copyright laws, this publication may not be reproduced or transmitted in any form, electronic or mechanical,
including photocopying, recording, storing in an information retrieval system, or translating, in whole or in part,
without the prior written consent of National Instruments Corporation.
Trademarks
BridgeVIEW™, FieldPoint™, LabVIEW™, and Lookout™ are trademarks of National Instruments Corporation.
Product and company names listed are trademarks or trade names of their respective companies.
WARNING REGARDING MEDICAL AND CLINICAL USE OF NATIONAL INSTRUMENTS PRODUCTS
National Instruments products are not designed with components and testing intended to ensure a level of reliability
suitable for use in treatment and diagnosis of humans. Applications of National Instruments products involving
medical or clinical treatment can create a potential for accidental injury caused by product failure, or by errors on the
part of the user or application designer. Any use or application of National Instruments products for or involving
medical or clinical treatment must be performed by properly trained and qualified medical personnel, and all traditional
medical safeguards, equipment, and procedures that are appropriate in the particular situation to prevent serious injury
or death should always continue to be used when National Instruments products are being used. National Instruments
products are NOT intended to be a substitute for any form of established process, procedure, or equipment used to
monitor or safeguard human health and safety in medical or clinical treatment.
Table of
Contents
About This Manual
How to Use This Manual Set........................................................................................ix
Organization of This Manual........................................................................................x
Conventions Used in This Manual................................................................................x
Related Documentation.................................................................................................xi
Customer Communication ............................................................................................xi
Chapter 1
FP-1000 Connects to RS-232 .......................................................................................1-1
FP-1001 Connects to RS-485 .......................................................................................1-2
Chapter 2
Installation and Configuration
Installing the Network Module.....................................................................................2-1
Removing the Network Module ...................................................................................2-2
Connecting Terminal Bases..........................................................................................2-2
Connecting the FP-1000 to the Network ......................................................................2-3
Connecting the FP-1001 to the Network ......................................................................2-4
Connecting to the Serial Ports ......................................................................................2-5
RS-232 Interface Specifications.....................................................................2-6
RS-485 Interface Specifications.....................................................................2-7
RS-485 Network Termination and Biasing ....................................................2-7
Configuring the Network Module.................................................................................2-9
Setting the Network Address..........................................................................2-10
Setting the Baud Rate.....................................................................................2-12
Connecting Power to the FP-1000 or FP-1001.............................................................2-12
Calculating Power for a FieldPoint Bank .....................................................................2-13
Chapter 3
Feature Set Description
High-Speed Local Bus..................................................................................................3-1
Network Watchdog Timer ............................................................................................3-1
© National Instruments Corporation
v
FieldPoint FP-1000/FP-1001 User Manual
Table of Contents
Programmable Power-Up State.................................................................................... 3-3
HotPnP During Power-Up ............................................................................. 3-4
HotPnP During Operation.............................................................................. 3-5
Inserting New I/O Modules ............................................................. 3-5
Replacing I/O Modules.................................................................... 3-5
Power-On Self Test (POST)......................................................................................... 3-6
Chapter 4
Using the FieldPoint Software
Using the FieldPoint Explorer...................................................................................... 4-2
Using the FieldPoint Server with LabVIEW................................................................ 4-3
Using the FieldPoint Server with LabWindows/CVI................................................... 4-3
Using the FieldPoint Lookout Driver........................................................................... 4-4
Appendix A
Specifications
Appendix B
Customer Communication
Glossary
Index
Figures
Figure 2-1. DIN Rail Clip in the Unlocked Position................................................ 2-1
Figure 2-3. Locking the FieldPoint Network Module onto a DIN Rail................... 2-2
Figure 2-4. Connecting Terminal Bases................................................................... 2-3
Figure 2-5. Host Computer Connected to One FP-1000 and Two FP-1001
Network Modules.................................................................................. 2-4
Figure 2-6. Host Computer Connected to Three FP-1001 Network Modules ......... 2-5
Figure 2-7. RS-232 Connector Pinout for the FP-1000 ........................................... 2-6
FieldPoint FP-1000/FP-1001 User Manual
vi
© National Instruments Corporation
Table of Contents
Figure 2-8. RS-485 Connector Pinout for the FP-1000 and FP-1001 ......................2-7
Figure 2-10. Typical Signal Connections for Host Computer Connected to
Figure 2-11. Typical Signal Connections for Host Computer Connected to
Multiple FP-1001 Network Modules.....................................................2-9
Figure 2-12. Address and Baud Rate Switch..............................................................2-9
Figure 3-1. LEDs on the FP-1000 and FP-1001.......................................................3-7
Tables
Table 2-1.
Network Modules ..................................................................................2-11
Baud Rate Switch Settings for the FP-1000 and FP-1001
Table 2-2.
Network Modules ..................................................................................2-12
Table 3-1.
Table 3-2.
Module Configuration Results After HotPnP Replacement..................3-6
STATUS LED Flashes and Corresponding Error Conditions...............3-8
© National Instruments Corporation
vii
FieldPoint FP-1000/FP-1001 User Manual
About
This
Manual
This manual describes how to install and use the FieldPoint FP-1000
and FP-1001 network modules.
How to Use This Manual Set
Operating
Instructions
for Modules
and Bases
FieldPoint Server
Online Help
Installation
Specifications
FieldPoint
Programmer
Reference
Manual
FieldPoint
User Manual
Network Connection,
Hardware
Configuration, and
Feature Set
Description
Command Syntax
© National Instruments Corporation
ix
FieldPoint FP-1000/FP-1001 User Manual
About This Manual
Organization of This Manual
This manual is organized as follows:
•
•
Chapter 1, FP-1000 and FP-1001 Network Module Overview,
Chapter 2, Installation and Configuration, describes how to install
RS-232 or RS-485 network, and connect power to the network
module.
•
•
•
•
Chapter 3, Feature Set Description, describes the feature set for the
FP-1000 and FP-1001 network modules.
Chapter 4, Using the FieldPoint Software, describes how to use the
FieldPoint hardware with various servers and software packages.
Appendix A, Specifications, describes the specifications of the
FP-1000 and FP-1001 network modules.
Appendix B, Customer Communication, contains forms you can
use to request help from National Instruments or to comment on our
products and manuals.
•
•
The Glossary contains an alphabetical list and description of terms
used in this manual, including abbreviations, acronyms, metric
prefixes, mnemonics, and symbols.
The Index contains an alphabetical list of key terms and topics in
this manual, including the page number where you can find each
one.
Conventions Used in This Manual
The following conventions are used in this manual:
This icon to the left of bold italicized text denotes a note, which alerts
you to important information.
This icon to the left of bold italicized text denotes a caution, which
advises you of precautions to take to avoid injury, data loss, or a
system crash.
!
bold
Bold text denotes the names of menus, menu items, parameters, dialog
box, dialog box buttons or options, icons, windows, Windows 95 tabs,
or LEDs.
bold italic
Bold italic text denotes a note, caution, or warning.
FieldPoint FP-1000/FP-1001 User Manual
x
© National Instruments Corporation
About This Manual
italic
Italic text denotes emphasis, a cross reference, or an introduction to a
key concept. This font also denotes text from which you supply the
appropriate word or value, as in Windows 3.x.
italic monospace
monospace
Italic text in this font denotes that you must supply the appropriate
words or values in the place of these items.
Text in this font denotes text or characters that should literally enter
from the keyboard, sections of code, programming examples, and
syntax examples. This font is also used for the proper names of disk
drives, paths, directories, programs, subprograms, subroutines, device
names, functions, operations, variables, filenames and extensions, and
for statements and comments taken from programs.
Related Documentation
The following documents contain information that you may find helpful
as you read this manual:
•
Operating Instructions (for network module, terminal bases, and
I/O modules)
•
FieldPoint Server Online Help
Customer Communication
National Instruments wants to receive your comments on our products
and manuals. We are interested in the applications you develop with our
products, and we want to help if you have problems with them. To make
it easy for you to contact us, this manual contains comment and
configuration forms for you to complete. These forms are in
Appendix B, Customer Communication, at the end of this manual.
© National Instruments Corporation
xi
FieldPoint FP-1000/FP-1001 User Manual
Chapter
FP-1000 and FP-1001
Network Module Overview
1
This chapter provides an overview of the FieldPoint network modules.
The FP-1000 FieldPoint network module connects an industrial RS-232
network to FieldPoint I/O modules. The FP-1001 FieldPoint network
module connects an industrial RS-485 network to FieldPoint I/O
modules.
The FP-1000 and FP-1001 support standard commands (subset of
Optomux command set), and a set of extended commands to completely
support the FieldPoint I/O modules. Both network modules can co-exist
with other Optomux devices on the same network.
The FP-1000 and FP-1001 use the Optomux protocol. Therefore, after
you have configured the FieldPoint bank (network module and I/O
modules), you can use any application software that supports Optomux
to communicate with FieldPoint modules in the bank.
In a distributed application, many FieldPoint banks are networked
together. You can network up to 25 FieldPoint banks to each
RS-232/RS-485 port of your host computer. Each bank can contain up
to nine I/O modules, thus connecting up to 225 I/O modules per RS-232
(or RS-485) port in your host computer. You can further increase your
field I/O count by using more RS-232/RS-485 ports in your host
computer.
FP-1000 Connects to RS-232
The FP-1000 connects directly to the RS-232 port that is available on
most host computers. Since RS-232 is a point-to-point network that
allows connection to only one device, the FP-1000 provides an RS-485
repeater so that you can build a network with multiple FieldPoint banks.
© National Instruments Corporation
1-1
FieldPoint FP-1000/FP-1001 User Manual
Chapter 1
FP-1000 and FP-1001 Network Module Overview
FP-1001 Connects to RS-485
The FP-1001 FieldPoint network module connects directly to an
RS-485 adapter card that is installed in your host computer. Since
RS-485 is inherently a multidrop network, the FP-1001 does not
provide a separate RS-485 repeater. You can network multiple FP-1001
modules in multidrop fashion.
The FP-1001 communicates over RS-485, utilizing full-duplex mode. It
is optically isolated, which prevents fault coupling between the RS-485
network and the FP-1001.
FieldPoint FP-1000/FP-1001 User Manual
1-2
© National Instruments Corporation
Chapter
Installation and
Configuration
2
This chapter describes how to install and configure your FieldPoint
network module, connect it to an RS-232 or RS-485 network, and
connect power to the network module.
Installing the Network Module
The FieldPoint network modules have rugged, simple clips for
mounting reliably onto a standard 35 mm DIN rail. Follow these steps
to mount the network module onto a DIN rail. Terminal bases must be
connected to the network module before power is applied.
1. Use a flat-bladed screwdriver to open the DIN rail clip to the
unlocked position, as shown in Figure 2-1.
Rail Clip Unlocked
Rail Clip Locked
Figure 2-1. DIN Rail Clip in the Unlocked Position
2. Hook the lip on the rear of the network module onto the top of a
35 mm DIN rail and press the network module down onto the DIN
rail as shown in Figure 2-2.
Local Bus
Connector
Cover
DIN Rail
Press
Figure 2-2. Installing the Network Module onto a DIN Rail
© National Instruments Corporation
2-1
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
3. Slide the network module to the desired position on the DIN rail.
After the module is in position, push the rail snap into the locked
position to lock the module in place on the DIN rail, as shown in
Figure 2-3.
Network
Module
DIN
Rail
Rail Snap Unlocked
(Position Module Along DIN Rail)
Rail Snap
Locked
Figure 2-3. Locking the FieldPoint Network Module onto a DIN Rail
Removing the Network Module
To remove a network module, unlock it from the DIN rail by placing a
screwdriver in the slot on the rail snap and opening it to the unlocked
position as shown in Figure 2-1. Then disconnect the terminal base
from the network module’s local bus connector, and lift the module off
of the rail.
Connecting Terminal Bases
Note:
Ensure that power is not applied to the network module, before you install
or remove terminal bases.
1. Remove the protective cover from the network module’s local bus
connector (see Figure 2-2).
2. Install the terminal base onto the DIN rail in the same way you
installed the network module. Refer to the operating instructions
for the FP-TB-1/2 more information on how to install your terminal
base onto the DIN rail.
FieldPoint FP-1000/FP-1001 User Manual
2-2
© National Instruments Corporation
Chapter 2
Installation and Configuration
3. Attach the terminal base to the network module by firmly mating
4. To add more terminal bases, install them on the rail and mate their
local bus connectors together.
5. Place the protective cover that you removed from the network
module on the last terminal base on the bank, as shown in
Figure 2-4.
Local Bus Connectors
Firmly Mated
Protective
Cover
Rail Snap
Locked
DIN
Rail
Figure 2-4. Connecting Terminal Bases
Connecting the FP-1000 to the Network
This section describes the network configurations possible with the
FP-1000 FieldPoint network module. The connector pinouts are
described in the RS-232 Interface Specifications and RS-485 Interface
Specifications sections later in this chapter.
Connect the RS-232 port of the FP-1000 to your host computer’s
RS-232 port. Use a 9-pin Dsub male-to-female “straight-through”
cable. Do not use a null modem cable (usually female-to-female).
You can connect only one FP-1000 network module for each RS-232
port in your host computer. You can add more FieldPoint banks without
using more RS-232 ports of your host computer, by connecting one or
more (up to 24) FP-1001 network modules to the RS-485 repeater port
of the FP-1000. This network configuration is shown in Figure 2-5.
© National Instruments Corporation
2-3
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
Host Computer
FP-1001
FP-1001
FP-1000
RS-485
RS-232
Figure 2-5. Host Computer Connected to One FP-1000 and Two FP-1001
Network Modules
Connecting the FP-1001 to the Network
This section describes the network configurations possible with the
FP-1001 FieldPoint network module. The connector pinouts are
described in the RS-485 Interface Specifications section later in this
chapter.
One option for connecting the FP-1001 is to connect it to the RS-485
repeater port of an FP-1000 as shown in Figure 2-5. An alternative
method is to connect the FP-1001 directly to your host computer, if your
host computer provides an RS-485 interface (contact National
Instruments for information about available RS-485 hardware). You
can connect up to 25 FP-1001 network modules to each RS-485 port on
the host computer. This network configuration is shown in Figure 2-6.
FieldPoint FP-1000/FP-1001 User Manual
2-4
© National Instruments Corporation
Chapter 2
Installation and Configuration
Host Computer with
RS-485 Board Installed
FP-1001
FP-1001
FP-1001
RS-485
Figure 2-6. Host Computer Connected to Three FP-1001 Network Modules
The multidrop topology used in the networking configurations provides
protection against power failures at individual FieldPoint banks. It
eliminates the possibility that a power failure at one FP-1001 bank
might affect the communication between other banks in your network.
Because the FP-1000 provides an RS-485 repeater, a power failure at
that bank will affect communications.
Connecting to the Serial Ports
The following sections give information about the RS-232 and RS-485
ports on the network modules, and how to connect to them.
The RS-232 port on the FP-1000 network module is a full-duplex
interface. The RS-485 port on the FP-1000 and FP-1001 network
modules are optically isolated, full-duplex interfaces.
Caution: The RS-485 interface on both the FP-1000 and the FP-1001 modules is
isolated from the rest of the FieldPoint system, including the power supply,
backplane, and the RS-232 interface on the FP-1000. It is isolated with a
galvanic and optical isolation barrier, which has been designed and tested
to withstand fault voltages of up to 2500 Vrms. However, the safety rating
of this barrier is only for working voltages of up to 250 Vrms. Do not use
the isolation barrier of the RS-485 interface as a way to protect human
contact from common mode voltages of more than 250 Vrms. Also note that
while the RS-232 interface on the FP-1000 is isolated from the RS-485
interface, it is NOT isolated from the power supply inputs (the V and C
terminals).
!
© National Instruments Corporation
2-5
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
Both serial interfaces are self-configured to use the following
parameters:
1 Start Bit, 8 Data Bits, 1 Stop Bit, No Parity
The supported baud rates are 300, 1200, 2400, 9600, 19200, 38400,
57600, and 115200. Refer to the Configuring the Network Module
section for information about setting the baud rate for your modules.
Host computer RS-232 ports and RS-485 interface boards provide FIFO
buffers for transmit and receive that help to decrease the overhead on
host computers. National Instruments recommends that you enable
these FIFO buffers in your host computer or RS-485 interface board for
best performance.
RS-232 Interface Specifications
RS-232 specifies a maximum cabling distance of 50 ft, but
improvements in line drivers and cabling technology often allow you to
design your network beyond the recommendations of the specification.
The RS-232 connector is 9-pin female Dsub connector whose pinout is
shown in Figure 2-7.
5
4
3
2
1
9
8
7
6
Legend:
NC = Not Connected
GND = Ground
RX = Recieve
TX = Transmit
RTS = Request to Send
DSR = Data Set Ready
Figure 2-7. RS-232 Connector Pinout for the FP-1000
FieldPoint FP-1000/FP-1001 User Manual
2-6
© National Instruments Corporation
Chapter 2
Installation and Configuration
The FP-1000 does not use RS-232 hardware handshaking, but it still
asserts the RTS and DSR signals for host computers or software that
may require these signals. A host computer that does not use these
signals does not need to connect to them.
RS-485 Interface Specifications
RS-485 specifies a maximum cabling distance of 4000 ft, but
improvements in line drivers and cabling technology often allow you to
design your network beyond the recommendations of the specification.
If even longer distances are desirable, you can use RS-485 repeaters.
a T-junction. RS-485 stubs must be less than 3 in. long. However, you
can create longer stubs by using an RS-485 repeater to start the stub,
ensuring that the repeater is close to the junction.
The RS-485 connector is a 5-pin Combicon connector whose pinout is
shown in Figure 2-8.
1
2
3
4
5
Figure 2-8. RS-485 Connector Pinout for the FP-1000 and FP-1001
RS-485 Network Termination and Biasing
not anywhere else. At each end bank, termination resistors should be
installed between the RX pair and between the TX pair. These network
terminating resistors are nominally 120 Ω and are provided in your kit.
To install them, twist the resistor leads with the RS-485 signal wires and
then insert them into the RS-485 Combicon adapter as shown in
Figure 2-9. The 120 Ω resistor in the figure is a terminating resistor.
© National Instruments Corporation
2-7
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
R X +
R X -
G N D
T X -
T X +
+
–
+
–
RS-485
Signal Pair
RS-485
Signal Pair
120 Ω
120 Ω
Figure 2-9. Terminating RS-485 Using the Combicon Adapter
An RS-485 network also needs biasing resistors to protect the devices
on the network against noise during intervals when no RS-485 drivers
are transmitting on the network. The host computer’s RS-485 interface
normally has provision for such biasing resistors. When you are using
FP-1001 network modules directly connected to a host computer’s
computer’s RS-485 interface for better reliability and noise immunity.
more FP-1001 modules to the FP-1000.
Figures 2-10 and 2-11 show typical RS-232 and RS-485 signal
connections and termination for a FieldPoint network. Figure 2-10 is a
more detailed depiction of Figure 2-5, and Figure 2-11 is a more
detailed depiction of Figure 2-6.
FP-1001
FP-1001
TX
FP-1000
TX
RX
120Ω
120Ω
To Host
Computer's RS-232
Receive Input
RX
RX
TX
From Host
Computer's RS-232
Transmit Output
120Ω
120Ω
Ground
Connect the TX outputs of the FP-1001 to the RX inputs of the FP-1000,
and the RX inputs of the FP-1001 to the TX outputs of the FP-1000.
Figure 2-10. Typical Signal Connections for Host Computer Connected to One
FP-1000 and Multiple FP-1001 Network Modules
FieldPoint FP-1000/FP-1001 User Manual
2-8
© National Instruments Corporation
Chapter 2
Installation and Configuration
FP-1001
FP-1001
TX
FP-1001
+
–
RX
TX
RX
RX
TX
To Host
Computer's RS-485
Receive Input Pair (RX)
120Ω
120Ω
–
+
From Host
Computer's RS-485
Transmit Output Pair (TX)
120Ω
120Ω
Connect the TX outputs of the host computer to the RX inputs of the FP-1001,
and the RX inputs of the host computer to the TX outputs of the FP-1001.
FP-1001 Network Modules
Configuring the Network Module
Figure 2-12 shows the 8-position switch on the FP-1000 and FP-1001
FieldPoint network modules. Switches 1-5 set the network address, and
switches 6-8 set the baud rate.
1
2
3
4
5
6
7
8
Baud
Address Rate
1 2 3 4 5 6 7 8
Switch Cover
(Removed)
Figure 2-12. Address and Baud Rate Switch
© National Instruments Corporation
2-9
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
Follow these steps to set the address and baud rate for your network
module.
1. Choose and set a network address. Refer to the following section,
Setting the Network Address, for more information.
2. Choose and set the baud rate. For more information, refer to the
section, Setting the Baud Rate, later in this chapter.
3. Write your address and baud rate settings in the space provided on
the network module label.
4. Apply (or cycle) power to the bank, to enable the network module
for the new network address and baud rate.
5. Make the same address and baud rate changes in your FieldPoint
software. Refer to the FieldPoint software online help for more
information.
Setting the Network Address
Switches 1-5 set the network module address. The addresses of the
terminal bases in a FieldPoint bank are automatically configured by the
network module to be sequentially higher than the network module’s
address. For example, if the network module is set to address 20, the I/O
module in the terminal base adjacent to the network module is at
address 21, the next I/O module is at address 22, and so on. A terminal
not.
Note:
If you are connecting more than one network module to the same host
computer port, ensure that each network module has a unique address.
Table 2-1 shows the possible switch positions and the corresponding
address of the FieldPoint network module.
FieldPoint FP-1000/FP-1001 User Manual
2-10
© National Instruments Corporation
Chapter 2
Installation and Configuration
Table 2-1. Network Address Switch Settings for the FP-1000 and FP-1001 Network Modules
Switch
Positions 1 - 5
Network Module
Address (Decimal)
Switch
Positions 1 - 5
Network Module
Address (Decimal)
0
130
140
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
20
150
1 2 3 4 5 6 7 8
30
160
1 2 3 4 5 6 7 8
40
170
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
50
180
1 2 3 4 5 6 7 8
60
190
1 2 3 4 5 6 7 8
70
200
1 2 3 4 5 6 7 8
80
210
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
90
220
100
110
120
230
240
1 2 3 4 5 6 7 8
Other Settings
Not Allowed
1 2 3 4 5 6 7 8
© National Instruments Corporation
2-11
FieldPoint FP-1000/FP-1001 User Manual
Chapter 2
Installation and Configuration
Setting the Baud Rate
Switches 6-8 set the network module baud rate. Table 2-2 shows the
switch positions and the corresponding network baud rates of the
network module.
Note:
If you are connecting more than one network module to the same host
computer port, ensure that every network module’s baud rate setting is
identical.
Table 2-2. Baud Rate Switch Settings for the FP-1000 and FP-1001 Network Modules
Switch
Positions 6-8
Network Module
Baud Rate
Switch
Positions 6-8
Network Module
Baud Rate
300
19200
38400
57600
115200
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1200
2400
9600
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Connecting Power to the FP-1000 or FP-1001
An 11-30 VDC power supply is required by each FieldPoint network
and provides power for all the I/O modules in the bank. Therefore you
need not provide power separately to each FieldPoint I/O module in the
bank.
The power connector is a 4-pin screw terminal connector whose pinout
is shown in Figure 2-13.
FieldPoint FP-1000/FP-1001 User Manual
2-12
© National Instruments Corporation
Chapter 2
Installation and Configuration
V V
V
+
-
To Adjacent Terminal Base
(Optional Connection)
11-30 VDC
C C
C
Figure 2-13. FP-1000 and FP-1001 Power Connector Pinout
The two terminals labeled V are internally connected on the network
module, as are the two terminals labeled C. Power must be applied to
one V and C pair for operation of the FieldPoint bank. If you want to
power your field I/O devices from the same power supply, the second
V and C pair provides a convenient means of connecting power to the
V and C terminals of a terminal base. Figure 2-13 shows this optional
connection.
If your field I/O devices need to be powered separately, you can use the
terminals provided on each terminal base for such power supply
connections. Refer to the documentation that came with your terminal
base and I/O module for more information on powering your field I/O
devices.
Calculating Power for a FieldPoint Bank
The power requirements for a FieldPoint bank that uses an FP-1000 or
FP-1001 network module are calculated as follows:
Power = 1 watt + 1.15 * ∑(I/O Module Consumption)
The operating instructions for each FieldPoint I/O module contain
power consumption information.
© National Instruments Corporation
2-13
FieldPoint FP-1000/FP-1001 User Manual
Chapter
3
Feature Set Description
This chapter describes the feature set for the FP-1000 and FP-1001
network modules.
Both the FP-1000 and FP-1001 have an identical feature set, so this
chapter uses the term network module to refer to either one. Any specific
differences are noted.
High-Speed Local Bus
The network modules provide a high-speed local bus for
communication to the I/O modules in the bank. The high-speed local
bus has low overhead that enables fast response to commands from the
host computer.
Network Watchdog Timer
The network module can detect unexpected periods of network
inactivity and respond to it in a user-defined way. The network
watchdog timer feature enables you to guard your system against
failures in the network connection, cables, or host computer, and to put
the channel outputs in a user-defined state (the watchdog state) if such
failures do occur.
You can set the watchdog output values to be different from the
power-up output values. Some system applications do not differentiate
between power-up output values and watchdog output values, while
other applications treat the two conditions differently. The network
module supports both types of applications.
By default, the watchdog timer for the bank is disabled on power up. To
use the watchdog timer, set up the following parameters. You can use
either the FieldPoint Explorer software or the FieldPoint command set.
•
•
Watchdog data value for each channel.
Watchdog data enable/disable status for each channel.
© National Instruments Corporation
3-1
FieldPoint FP-1000/FP-1001 User Manual
Chapter 3
Feature Set Description
•
•
Watchdog enabled/disabled status for each I/O module.
Watchdog timeout value for the bank.
Note:
Each bank has only one watchdog timeout value that is common for all the
modules in that bank. In addition, the current watchdog timeout value is
not stored when you store the SnapShot.
SnapShot Feature
Many applications require that, upon startup, the system’s I/O power up
with user-specified configuration and output levels rather than factory
default settings. The SnapShot feature provides you with a single-step
method to store the current state of your FieldPoint bank for use as the
power-up state of the bank.
If you subsequently enable the SnapShot feature, you can ensure that
your system will power up with the configuration and output levels that
you specified when storing the SnapShot.
Prior to storing the SnapShot, you should bring all the channels to the
desired power-up settings. You can use either the FieldPoint Server
software or the FieldPoint command set to change the configuration of
the FieldPoint bank, and then store the SnapShot. The SnapShot stores
all the following information in a single step:
•
•
•
Attribute and range settings of each channel.
Output values of each channel.
Watchdog data values of each channel. See the Network Watchdog
Timer section in this chapter for more information.
•
•
Watchdog data enabled (or disabled) status for each channel. See
the Network Watchdog Timer section in this chapter for more
information.
Watchdog enabled (or disabled) status of each module. See the
Network Watchdog Timer section in this chapter for more
information.
After you store the SnapShot information, you can still choose whether
the network module uses that stored information during future
power-ups. Enable the SnapShot feature if you want the FieldPoint bank
to power-up with the stored SnapShot information.
FieldPoint FP-1000/FP-1001 User Manual
3-2
© National Instruments Corporation
Chapter 3
Feature Set Description
If you have enabled the SnapShot feature, the network module restores
the stored settings to all I/O modules and channels in the bank every
time you power up, until you disable the SnapShot feature. If the
SnapShot feature is disabled, the FieldPoint bank will power up with
factory-default settings.
At some time you might want to change the stored SnapShot
information. To make incremental changes in the stored SnapShot
information, you can use the features described in the next section,
Programmable Power-Up State.
Note:
Note:
The current watchdog timeout value for the FieldPoint bank is not saved
when you store the SnapShot.
The SnapShot feature inherently requires that the entire FieldPoint bank
be at your desired power-up state, since when you store the SnapShot
information, the current settings of the entire bank are stored for use at
future power-ups.
Programmable Power-Up State
The SnapShot feature described in the SnapShot section provides you
with a single-step method to store the current state of the FieldPoint
bank for use as the power-up state. The FieldPoint network module
provides an alternative method to define power-up states that allows
you to store the SnapShot information with more flexibility, as
described in this section.
The Programmable Power-Up State feature enables you to define the
power-up configuration on a module-by-module basis. In addition, you
do not need to actually set any of the channels to the desired power-up
state. You can therefore define the power-up states regardless of the
current settings of any channel of a module.
Optionally, you can utilize the Programmable Power-Up State feature
to incrementally modify previously stored SnapShot information.
If you subsequently enable the SnapShot feature, you can ensure that
your system will power up with the configuration and output levels that
you specified when storing the Programmable Power-Up States.
You can utilize the Programmable Power-Up State feature to
individually store the following information. You can use either the
FieldPoint Explorer software or the FieldPoint command set.
© National Instruments Corporation
3-3
FieldPoint FP-1000/FP-1001 User Manual
Chapter 3
Feature Set Description
•
•
•
Attribute and range settings of each channel.
Output values of each channel.
Watchdog data value of each channel. See the Network Watchdog
Timer section in this chapter for more information.
•
•
Watchdog data enabled (or disabled) status for each channel. See
the Network Watchdog Timer section in this chapter for more
information.
Watchdog timer enabled (or disabled) status of each module. See
the Network Watchdog Timer section in this chapter for more
information.
•
•
•
Power-up watchdog timeout value for the FieldPoint bank.
The turn-around delay for each module.
The hot-swap reporting mode for the FieldPoint stack. See the
HotPnP section for more information on the hot-swap reporting
mode.
If you have enabled the SnapShot feature, the network module restores
your desired settings to all I/O modules and channels in the bank every
time you power up, until you disable the SnapShot feature.
HotPnP (Hot Plug and Play)
The HotPnP feature simplifies system installation, configuration, and
maintenance. With the HotPnP feature, you can remove or insert I/O
modules into the FieldPoint terminal bases while power is on, even if
the system is already engaged in network activity. You do not need to
power down the entire system or even a bank to insert, remove, or
replace I/O modules. In addition, you do not need to change the
operation of the host computer or software to use the HotPnP feature.
When you insert an I/O module with the power on, it is automatically
recognized, configured, and made available on the network. The
following sections describe how the HotPnP feature works under
different conditions.
Note:
An I/O module can be hot-inserted only if an empty terminal base is already
available in the bank. You should not add or remove terminal bases while
power is applied to the bank.
FieldPoint FP-1000/FP-1001 User Manual
3-4
© National Instruments Corporation
Chapter 3
Feature Set Description
HotPnP During Power-Up
Upon power-up, the network module automatically uploads an
electronic data sheet (EDS) from each I/O module in its bank. The
network module then configures each I/O module in the bank to factory
default settings in the module’s EDS, or stored SnapShot settings if the
SnapShot feature is enabled.
HotPnP During Operation
You may need to insert or replace one or more I/O modules in a bank
while your system is operational (power is on and the network may or
may not be active).
Inserting New I/O Modules
When a new I/O module is inserted, the network module automatically
uploads the EDS and configures the I/O module to factory default
settings in the module’s EDS, or to stored SnapShot settings if the
SnapShot feature is enabled. This configuration is accomplished
without any intervention from the host computer or software.
While one or more new I/O modules in a bank are being serviced by the
HotPnP feature, the other I/O modules in the bank remain fully
operational and accessible on the network without any interruptions. As
soon as the network module configures the new I/O module via the
HotPnP service, that I/O module becomes automatically accessible on
the network.
Replacing I/O Modules
When an I/O module is removed, the network module does not
undertake any special course of action for the bank. The host computer
(or the software executing on it) may be unaware that the I/O module is
missing, and may continue to send commands to the missing I/O
module. Each command returns an error response, but the network
module remembers the commands sent to the missing I/O module.
When a new I/O module is connected in place of the one that was
removed, the network module first verifies that the replacement I/O
module is compatible with the one that was removed. If the I/O module
is the same as, or is compatible with, the one removed, the network
module configures the replacement I/O module with its predecessor’s
configuration and output value settings. It also applies the effects of any
commands sent by the host computer while the I/O module was missing.
© National Instruments Corporation
3-5
FieldPoint FP-1000/FP-1001 User Manual
Chapter 3
Feature Set Description
If the replacement module is incompatible with the one that was
removed, the network module looks at the information stored in the
compatible with the information in the SnapShot, the network module
configures the replacement module with the SnapShot configuration.
Otherwise, the network module configures the replacement module to
factory default settings.
Table 3-1 shows how modules are configured after HotPnP
replacement.
Table 3-1. Module Configuration Results After HotPnP Replacement
Replacement Module
SnapShot
Feature
Configuration After
HotPnP
Replacement Module
Enabled/
Disabled
Compatible with the
removed module
Same as the configuration
of the removed module
Disabled
Incompatible with the
removed module
Factory default
configuration of
replacement module
Enabled
Incompatible with the
removed module but
compatible with the
SnapShot information
Same as the configuration
stored in the SnapShot
Enabled/
Disabled
Incompatible with the
removed module and
incompatible with the
stored SnapShot
Factory default
configuration of
replacement module
information
While one or more replacement I/O modules in the bank are being
serviced by the HotPnP feature, the other I/O modules in the bank
remain fully operational and accessible on the network without any
interruptions. As soon as the network module configures a replacement
I/O module via the HotPnP service, that I/O module becomes
automatically accessible on the network.
FieldPoint FP-1000/FP-1001 User Manual
3-6
© National Instruments Corporation
Chapter 3
Feature Set Description
Power-On Self Test (POST)
The power-on self test (POST) is a test suite that the network module
performs at power up to verify its own operational status. The test is
non-invasive and therefore does not affect the operation of the network,
nor does it affect any of your field wiring connected to the terminal
bases in the bank.
If the self-test suite fails, the network module does not participate in the
network communication traffic, thereby eliminating potential conflicts
with the other banks in your network.
The network module indicates POST failure via the STATUS LED.
LED Indicators
The network module has four LED indicators: POWER, NETWORK,
ACCESS, and STATUS. Figures 3-1 shows the LEDs on the network
modules.
ADDRESS
BAUD
TSU
A
P
K
A
ST
ADDRESS
BAUD
TSU
A
P
K
A
ST
Figure 3-1. LEDs on the FP-1000 and FP-1001
The green POWER LED is lit while the network module is powered up.
This LED indicates that the power supply connected to the network
module is acceptable, and that the network module is supplying power
to the I/O modules.
© National Instruments Corporation
3-7
FieldPoint FP-1000/FP-1001 User Manual
Chapter 3
Feature Set Description
The yellow NETWORK LED is lit during transmissions from the host
computer on the network. This LED indicates that the network module
is receiving from the network, and that the communication wires to it
are not broken. The NETWORK LED gets brighter as activity on the
network increases.
The yellow ACCESS LED flashes when the network module or any of
the I/O modules in its bank respond to the host computer. This LED
indicates that a module in the bank was addressed by a correctly
formatted command, and that the module is responding to that
command (either with a success or error response).
The red STATUS LED is lit when the network module detects a failure.
If STATUS is not lit, the network module has not detected a failure. The
network module indicates specific error conditions by flashing
STATUS a specific number of times. Table 3-2 describes the STATUS
LED flashing sequences and the corresponding error condition.
Table 3-2. STATUS LED Flashes and Corresponding Error Conditions
Number of
Flashes
0 (stays lit)
1
The network module initialization failed.
The network module address switch is incorrectly
configured. Refer to the Setting the Network Address
section in Chapter 2, Installation and Configuration.
2
3
The network module has detected an error in the
terminal bases in the bank. Check whether there are
more than nine terminal bases (maximum allowed) in
the bank or whether removing one or more terminal
bases eliminates the error condition.
The network module has detected an irrecoverable
internal error.
FieldPoint FP-1000/FP-1001 User Manual
3-8
© National Instruments Corporation
Chapter
Using the FieldPoint
Software
4
This chapter describes how to use the FieldPoint hardware with various
servers and software packages.
FieldPoint Software Overview
Your FieldPoint software consists of three parts: the FieldPoint
Explorer, the FieldPoint Server, and a FieldPoint driver for Lookout.
The FieldPoint Explorer and the FieldPoint Server are both 32-bit
applications that run on Windows 95 or Windows NT.
•
•
•
The FieldPoint Explorer is a configuration utility for FieldPoint
modules. The FieldPoint Explorer configures the FieldPoint
hardware; the FieldPoint server, which is used with BridgeVIEW,
LabVIEW, LabWindows®/CVI, and OPC (OLE for Process
Control) client software; and the FieldPoint driver for the Lookout
software package.
The FieldPoint Server manages the communications between the
host computer and the FieldPoint hardware. The FieldPoint Server
is an interface to the BridgeVIEW, LabVIEW, and
LabWindows/CVI software packages from National Instruments.
In addition, it provides an OPC interface for other software
packages that have OPC client capability.
The FieldPoint driver for Lookout manages the communications
between a host computer running Lookout and the FieldPoint
hardware.
You can also choose to communicate with the FieldPoint system using
an Optomux compatible server, or by using the FieldPoint command
set. If you use either of these methods, refer the FieldPoint FP-1000 and
FP-1001 Programmer Reference Manual. You may, however, still use
the FieldPoint Explorer to configure the FieldPoint devices before
running your software.
© National Instruments Corporation
4-1
FieldPoint FP-1000/FP-1001 User Manual
Chapter 4
Using the FieldPoint Software
Using the FieldPoint Explorer
You can use the FieldPoint Explorer to accomplish the following tasks:
•
•
•
Configure the characteristics and hardware of a FieldPoint device
network
Configure the tag name space and I/O items of the FieldPoint
Server
Write and read I/O values to and from the FieldPoint hardware
After configuring the FieldPoint system with FieldPoint Explorer, you
can save the configuration in an Industrial Automation Kernel (IAK)
file (.iakfile). This file contains the configuration information
necessary for the FieldPoint Server.
The FieldPoint Explorer includes online help. To get started, run the
FieldPoint Explorer program and select FieldPoint from the Help menu.
Using the FieldPoint Server with BridgeVIEW
To use the FieldPoint Server with BridgeVIEW, you must export the
configuration information saved by the FieldPoint Explorer in an .iak
file to the BridgeVIEW server configuration data store, the Common
Configuration Database (CCDB). After you have configured and tested
your FieldPoint network from FieldPoint Explorer, select Export to
Active CCDB from the File menu option to export the current IAK
configuration to BridgeVIEW.
Once the IAK configuration information is exported to BridgeVIEW,
you can automatically generate BridgeVIEW tags from your FieldPoint
items by launching the BridgeVIEW Tag Configuration Editor and
clicking on the Tag Wizard button.
Refer to the BridgeVIEW user manual for more information about
BridgeVIEW server configuration, the tag configuration editor, the tag
wizard, and the active CCDB files.
Note:
If you edit, rename, or move your .iak configuration file after you export
it to the BridgeVIEW active CCDB, you must export the .iak
configuration file again. Also, if you select another CCDB file as the active
CCDB, you must export the .iak configuration file again, to the newly
selected active CCDB file.
FieldPoint FP-1000/FP-1001 User Manual
4-2
© National Instruments Corporation
Chapter 4
Using the FieldPoint Software
Using the FieldPoint Server with LabVIEW
To use the FieldPoint server from LabVIEW, first configure and test
your FieldPoint device network from FieldPoint Explorer. After you are
satisfied with the configuration, save your .iak configuration file. You
can then access named FieldPoint item values using the LabVIEW
FieldPoint Server Interface.
The LabVIEW FieldPoint Server Interface consists of seven VIs that
are used as an interface to the FieldPoint Server, as well as example VIs
that demonstrate the use of this interface.
•
The FP Open.vi and the FP Close.vi are used to open and close a
communications session to the FieldPoint server, using the
configuration information stored in an IAK file.
•
•
•
The FP Create Tag.vi is used to establish a communications session
with an I/O point defined in the IAK file.
After establishing this session, use the FP Read.vi, FP Write.vi, or
FP Advise.vi to communicate with the device.
The FP Get Configuration Info.vi is used to read the names of
communication resources, devices, and I/O items defined in the
IAK file.
During the FieldPoint Server installation, these VIs are installed and
made available in the LabVIEW function palette. For more information
on how to use these functions or the example VIs, refer to the file
Fplvreadme.wri that is installed with the FieldPoint Server, or refer
to the FieldPoint Server online help.
Using the FieldPoint Server with LabWindows/CVI
The LabWindows/CVI interface to the FieldPoint Server is an
instrument driver that has C functions similar to the VIs in the
LabVIEW FieldPoint Server interface. This instrument driver is
installed with the FieldPoint Server if LabWindows/CVI was already
installed on the computer.
After opening a session to the FieldPoint network using the
configuration information in an IAK file, you may either read or write
data using blocking calls or using callbacks. The function panels for
each of these C routines includes information on how to use the
functions.
© National Instruments Corporation
4-3
FieldPoint FP-1000/FP-1001 User Manual
Chapter 4
Using the FieldPoint Software
Using the FieldPoint Lookout Driver
The FieldPoint Lookout driver uses the configuration information in the
IAK file created by the FieldPoint Explorer for its own configuration.
The tag names used with the FieldPoint Lookout driver are the same as
the names assigned using FieldPoint Explorer. There is a separate disk
in your kit that contains the FieldPoint Lookout driver. This disk also
contains documentation for this driver in the lkreadme.wrifile.
Using FieldPoint with Optomux Servers
The protocol used by FieldPoint is compatible with the Optomux
protocol, and you may use Optomux servers to communicate with the
FieldPoint system. However, Optomux servers do not include
provisions for setting all the configurable parameters of a FieldPoint
system (such as input ranges and power up settings). Thus, you should
use FieldPoint Explorer to set up (and optionally store using SnapShot)
the configuration of the FieldPoint hardware before using an Optomux
server.
Refer to the FieldPoint FP-1000 and FP-1001 Programmer Reference
Manual for a description of which Optomux commands are supported,
and how to scale the data returned when using this protocol.
FieldPoint FP-1000/FP-1001 User Manual
4-4
© National Instruments Corporation
Appendix
A
Specifications
This appendix describes the specifications of the FP-1000 and FP-1001
network modules.
All FieldPoint network modules undergo extensive testing for operating
under rugged environmental conditions that exist in industrial
applications. FieldPoint network modules are designed and tested for
immunity and susceptibility, as well as for emissions.
Network
FP-1000 ..............................................1 RS-232 port, 1 RS-485
repeater port
FP-1001 ..............................................1 RS-485 port
Baud Rates..........................................300, 1200, 2400, 9600, 19200,
38400, 57600, 115200
(switch settable)
Communication Parameters ................1 Start Bit, 8 Data Bits, 1 Stop
Bit, No Parity
Integrity ..............................................Checksum
FP-1000 .....................................50 ft (nominal)*
FP-1001 .....................................4000 ft (nominal)*
* Refer to the RS-232 Interface Specifications and RS-485 Interface
Specifications sections in Chapter 2, Installation and
Configuration.
Maximum Terminal Bases per Bank ...9
Maximum Number of Banks ...............25
RS-232/RS-485 Interface Chips ..........15 kV ESD, Low noise and Slew
rate interface ICs
© National Instruments Corporation
A-1
FieldPoint FP-1000/FP-1001 User Manual
Appendix A
Specifications
RS-485 Isolation ................................ 2500 Vrms breakdown,
250 Vrms operational
Environment
Operating Temperature....................... –40° C to +70° C
Storage Temperature .......................... –55° C to + 100° C
Relative Humidity .............................. 5% to 90% noncondensing
Compliance
Electrical Safety................................. designed to meet IEC 1010
EMI Emissions/Immunity................... CISPR 11
FieldPoint FP-1000/FP-1001 User Manual
A-2
© National Instruments Corporation
Appendix
B
Customer Communication
For your convenience, this appendix contains forms to help you gather the information necessary to
help us solve your technical problems and a form you can use to comment on the product
documentation. When you contact us, we need the information on the Technical Support Form and the
configuration form, if your manual contains one, about your system configuration to answer your
questions as quickly as possible.
National Instruments has technical assistance through electronic, fax, and telephone systems to
quickly provide the information you need. Our electronic services include a bulletin board service,
an FTP site, a fax-on-demand system, and e-mail support. If you have a hardware or software
problem, first try the electronic support systems. If the information available on these systems
does not answer your questions, we offer fax and telephone support through our technical support
centers, which are staffed by applications engineers.
Electronic Services
Bulletin Board Support
National Instruments has BBS and FTP sites dedicated for 24-hour support with a collection of files
and documents to answer most common customer questions. From these sites, you can also download
the latest instrument drivers, updates, and example programs. For recorded instructions on how to use
the bulletin board and FTP services and for BBS automated information, call (512) 795-6990. You can
access these services at:
United States: (512) 794-5422
Up to 14,400 baud, 8 data bits, 1 stop bit, no parity
United Kingdom: 01635 551422
Up to 9,600 baud, 8 data bits, 1 stop bit, no parity
France: 01 48 65 15 59
Up to 9,600 baud, 8 data bits, 1 stop bit, no parity
FTP Support
To access our FTP site, log on to our Internet host, ftp.natinst.com, as anonymousand use
documents are located in the /supportdirectories.
© National Instruments Corporation
B-1
FieldPoint FP-1000/FP-1001 User Manual
Fax-on-Demand Support
Fax-on-Demand is a 24-hour information retrieval system containing a library of documents on a wide
range of technical information. You can access Fax-on-Demand from a touch-tone telephone at
(512) 418-1111.
E-Mail Support (currently U.S. only
)
You can submit technical support questions to the applications engineering team through e-mail at the
Internet address listed below. Remember to include your name, address, and phone number so we can
contact you with solutions and suggestions.
Telephone and Fax Support
National Instruments has branch offices all over the world. Use the list below to find the technical
support number for your country. If there is no National Instruments office in your country, contact the
source from which you purchased your software to obtain support.
Telephone
Fax
Australia
Austria
Belgium
Canada (Ontario)
Canada (Quebec)
Denmark
Finland
03 9879 5166
03 9879 6277
0662 45 79 90 0
02 757 00 20
905 785 0085
514 694 8521
45 76 26 00
09 725 725 11
01 48 14 24 24
089 741 31 30
2645 3186
03 5734815
02 413091
03 5472 2970
02 596 7456
5 520 2635
0662 45 79 90 19
02 757 03 11
905 785 0086
514 694 4399
45 76 26 02
09 725 725 55
01 48 14 24 14
089 714 60 35
2686 8505
France
Germany
Hong Kong
Israel
Italy
Japan
03 5734816
02 41309215
03 5472 2977
02 596 7455
5 520 3282
Korea
Mexico
Netherlands
Norway
Singapore
Spain
Sweden
Switzerland
Taiwan
0348 433466
32 84 84 00
2265886
91 640 0085
08 730 49 70
056 200 51 51
02 377 1200
01635 523545
512 795 8248
0348 430673
32 84 86 00
2265887
91 640 0533
08 730 43 70
056 200 51 55
02 737 4644
01635 523154
512 794 5678
United Kingdom
United States
FieldPoint System Configuration Form
Record the settings and revisions of your hardware and software on the line to the right of each item.
Complete a new copy of this form each time you revise your software or hardware configuration, and
use this form as a reference for your current configuration. Completing this form accurately also helps
us to answer your questions more efficiently.
Host Computer
Computer brand ________________ Model ________________ Processor __________________
Operating system (include version number ) ___________________________________________
Clock speed ______MHz RAM _____MB
Display adapter __________________________
Mouse ___yes ___no Mouse type _________________________________________________
National Instruments application software product ______________________ Version _________
Other application software product ___________________________________ Version ________
National Instruments server _________________________________________ Version ________
Other installed software that may use serial ports _______________________________________
_______________________________________________________________________________
Serial adaptor (COM port or adaptor card) used ________________________________________
Configuration _________________________________________________________________
Serial driver ______________________________________________________ Version ______
Configuration _________________________________________________________________
Serial port timeout value _____________ ms
Number of FieldPoint banks _______
COM Port
Number
Data Bits/Stop Bits/ Serial Hardware That
Parity Uses This Port
Baud Rate
TX/RX FIFOs
FieldPoint Software
List the applications and/or servers that you are using with the FieldPoint hardware ____________
_______________________________________________________________________________
FieldPoint Banks
Please use one page per FieldPoint bank.
Network module _____________________________________ Firmware revision ____________
Address __________________________________________ Baud rate __________________
Circle the state of the following items when your problem occurs:
LEDs POWER: ON/OFF NETWORK: ON/OFF ACCESS: ON/OFF STATUS: ON/OFF
SnapShot feature Enabled/Disabled
Watchdog timer Enabled/Disabled Timeout value ______ ms
Number of FieldPoint terminal bases ________________________________________________
Number of FieldPoint I/O modules __________________________________________________
Base
#
POWER READY
LED LED
Module Name*
Module Configuration Information
0
1
2
3
4
5
6
7
8
9
FP-1000/FP-1001
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
ON/OFF ON/OFF
* If a terminal base is present but no module is inserted, write “none.”
Technical Support Form
Photocopy this form and update it each time you make changes to your software or hardware, and use
the completed copy of this form as a reference for your current configuration. Completing this form
accurately before contacting National Instruments for technical support helps our applications
engineers answer your questions more efficiently.
If you are using any National Instruments hardware or software products related to this problem,
include the configuration forms from their user manuals. Include additional pages if necessary.
Name __________________________________________________________________________
Company _______________________________________________________________________
Address ________________________________________________________________________
_______________________________________________________________________________
Fax (___ )___________________ Phone (___ ) ________________________________________
Computer brand ________________ Model ________________ Processor___________________
Operating system (include version number) ____________________________________________
Clock speed ______MHz RAM _____MB
Mouse ___yes ___no Other adapters installed _______________________________________
Hard disk capacity _____MB Brand _____________________________________________
Display adapter __________________________
Instruments used _________________________________________________________________
_______________________________________________________________________________
National Instruments hardware product model __________ Revision ______________________
Configuration ___________________________________________________________________
National Instruments software product ____________________________Version ____________
Configuration ___________________________________________________________________
The problem is: __________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
List any error messages: ___________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
The following steps reproduce the problem:____________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
Documentation Comment Form
National Instruments encourages you to comment on the documentation supplied with our products.
This information helps us provide quality products to meet your needs.
Title:
FieldPoint™ FP-1000 and FP-1001 RS-232/RS-485 Network Module User Manual
Edition Date: July 1997
Part Number: 321631A-01
Please comment on the completeness, clarity, and organization of the manual.
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
If you find errors in the manual, please record the page numbers and describe the errors.
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
_______________________________________________________________________________
Thank you for your help.
Name _________________________________________________________________________
Title __________________________________________________________________________
Company _______________________________________________________________________
Address ________________________________________________________________________
_______________________________________________________________________________
Phone (___ )__________________________ Fax (___ ) _________________________________
Mail to: Technical Publications
Fax to: Technical Publications
National Instruments Corporation
(512) 794-5678
National Instruments Corporation
6504 Bridge Point Parkway
Austin, TX 78730-5039
Glossary
Prefix
m-
Meanings
milli-
Value
10–3
103
k-
kilo-
M-
mega-
106
%
percent
degrees
°
0x
Ω
precedes a hexadecimal number
ohms
bytes
B
bank
The combination of one FieldPoint network module and one or more
terminal bases and I/O modules.
C
celsius
DSR
EDS
EMI
FIFO
ft
Data Set Ready
electronic data sheet
electromagnetic interference
first-in-first-out
feet
g
grams
HotPnP
Hz
Hot Plug and Play
hertz
© National Instruments Corporation
G-1
FieldPoint FP-1000/FP-1001 User Manual
Glossary
I/O
input/output
IEC
in.
International Electrotechnical Commission
inches
LED
OPC
POST
RAM
RTS
V
Light-emitting diode
OLE for Process Control
power-on self test
random-access memory
Request to Send
Volts
VDC
Volts direct current
FieldPoint FP-1000/FP-1001 User Manual
G-2
© National Instruments Corporation
Index
serial port connections, 2-5 to 2-9
isolation of RS-485 interface (note),
2-5 to 2-6
A
ACCESS LED, 3-7
addresses, setting
RS-232 interface specifications,
2-6 to 2-7
RS-485 interface specifications,
2-7 to 2-9
address and baud rate, 2-9 to 2-10
network address, 2-10 to 2-11
unique address for each module (note), 2-10
terminal base connection, 2-2 to 2-3
connector pinouts
B
power connector (figure), 2-13
RS-232 ports (figure), 2-6
RS-485 ports (figure), 2-7
banks. See FieldPoint banks.
baud rate
address and baud rate switch settings
(figure), 2-9
customer communication, B-1 to B-2, xi
baud rate switch settings (figure), 2-12
setting for network module, 2-9 to 2-10
biasing resistors for RS-485 port, 2-8
BridgeVIEW software, using with FieldPoint
Server, 4-2
D
DIN rail clip
installing network module (figure), 2-1
locking FieldPoint network module
(figure), 2-2
bulletin board support, B-1
bus, high-speed local, 3-1
unlocked position (figure), 2-1
documentation
conventions used in manual, x-xi
how to use manual set, ix
organization of manual, x
related documentation, xi
C
configuration of network module, 2-9 to 2-12.
See also installation.
address and baud rate selection, 2-9 to 2-10
baud rate settings, 2-12
network address settings, 2-10 to 2-11
connections
E
electronic support services, B-1 to B-2
e-mail support, B-2
network connections
FP-1000, 2-3 to 2-4
FP-1001, 2-4 to 2-5
environment specifications, A-2
error conditions indicated by STATUS LED
(table), 3-8
© National Instruments Corporation
I-1
FieldPoint FP-1000/FP-1001 User Manual
Index
F
H
fax and telephone support, B-2
fax-on-demand support, B-2
feature set description, 3-1 to 3-8
high-speed local bus, 3-1
HotPnP (Hot Plug and Play), 3-4 to 3-6
LED indicators, 3-7 to 3-8
network watchdog timer, 3-1 to 3-2
power-on self test (POST), 3-6 to 3-7
Programmable Power-Up State, 3-3 to 3-4
SnapShot feature, 3-2 to 3-3
FieldPoint banks
HotPnP (Hot Plug and Play), 3-4 to 3-6
inserting new I/O modules, 3-5
module configuration results after
HotPnP replacement (table), 3-6
during operation, 3-5 to 3-6
overview, 3-4
during power-up, 3-4
replacing I/O modules, 3-5 to 3-6
I
installation, 2-1 to 2-13. See also configura-
tion of network module.
calculating power for bank, 2-13
maximum number of banks, 1-1
network watchdog timer, 3-1 to 3-2
SnapShot feature, 3-2 to 3-3
FieldPoint network modules. See also feature
set description.
connecting to network
FP-1000, 2-3 to 2-4
FP-1001, 2-4 to 2-5
HotPnP (Hot Plug and Play) features,
3-4 to 3-6
network module installation, 2-1 to 2-2
power connections for FP-1000 or
FP-1001, 2-12 to 2-13
calculating power for FieldPoint
bank, 2-13
removing network module, 2-2
serial port connections, 2-5 to 2-9
isolation of RS-485 interface (note),
2-5 to 2-6
overview, 1-1
specifications, A-1 to A-2
FieldPoint software, 4-1 to 4-4
FieldPoint Explorer, 4-2
FieldPoint Lookout driver, 4-4
Optomux Servers, 4-4
overview, 4-1
using FieldPoint Server
with BridgeVIEW, 4-2
with LabVIEW, 4-3
RS-232 interface specifications,
2-6 to 2-7
RS-485 interface specifications,
2-7 to 2-9
with LabWindows/CVI, 4-3
FP-1000
connecting to network, 2-3 to 2-4
connection to RS-232 port, 1-1
power connections, 2-12 to 2-13
FP-1001
terminal base connection, 2-2 to 2-3
I/O modules
inserting new, 3-5
connecting to network, 2-4 to 2-5
connection to RS-485 port, 1-2
power connections, 2-12 to 2-13
FTP support, B-1
module configuration results after
HotPnP replacement (table), 3-6
replacing, 3-5 to 3-6
FieldPoint FP-1000/FP-1001 User Manual
I-2
© National Instruments Corporation
Index
L
R
LabVIEW software, using with FieldPoint
Server, 4-3
removing FieldPoint network module, 2-2
RS-232 ports
LabWindows/CVI software, using with
FieldPoint Server, 4-3
LED indicators, 3-7 to 3-8
local bus, high-speed, 3-1
connector pinout (figure), 2-6
FP-1000 connection to, 1-1
interface specifications, 2-6 to 2-7
self-configuration parameters, 2-6
RS-485 ports
Combicon adapter for termination
(figure), 2-8
M
manual. See documentation.
connector pinout (figure), 2-7
FP-1001 connection to, 1-2
interface specifications, 2-7 to 2-9
isolation from FieldPoint system
(note), 2-5
network termination and biasing,
2-7 to 2-9
self-configuration parameters, 2-6
typical signal connections (figures),
2-8 to 2-9
N
network address, setting, 2-10 to 2-11
NETWORK LED, 3-7
network module. See FieldPoint network
modules.
network termination and biasing, RS-485
ports, 2-7 to 2-9
network watchdog timer, 3-1 to 3-2
S
O
serial ports. See RS-232 ports; RS-485 ports.
SnapShot feature, 3-2 to 3-3
software. See FieldPoint software.
specifications, A-1 to A-2
compliance, A-2
Optomux protocol, 1-1
Optomux Servers, using with FieldPoint
software, 4-4
environment, A-2
network, A-1 to A-2
STATUS LED, 3-8
switches
P
pinouts. See connector pinouts.
power connections, 2-12 to 2-13
calculating power for FieldPoint
bank, 2-13
address and baud rate switch (figure), 2-9
baud rate switch settings (figure), 2-12
network address switch settings
(figure), 2-11
pinout (figure), 2-13
POWER LED, 3-7
power-on self test (POST), 3-6 to 3-7
Programmable Power-Up State, 3-3 to 3-4
© National Instruments Corporation
I-3
FieldPoint FP-1000/FP-1001 User Manual
Index
T
technical support, B-1 to B-2
telephone and fax support, B-2
terminal base connection, 2-2 to 2-3
termination and biasing, RS-485 ports,
2-7 to 2-9
W
watchdog timer, 3-1 to 3-2
FieldPoint FP-1000/FP-1001 User Manual
I-4
© National Instruments Corporation
|