Multi Tech Systems Switch FR111 User Manual

Model FR111  
Single Port Frame Relay  
Access Device with 56K DSU  
Owner's Manual  
 
 
Owner'sManual  
82067401RevisionB  
MultiFRADTM100-Series(ModelNoFR111)  
This publication may not be reproduced, in whole or in part, without  
prior expressed written permission from Multi-Tech Systems, Inc. All  
rights reserved.  
Copyright © 1998, by Multi-Tech Systems, Inc.  
Multi-Tech Systems, Inc. makes no representations or warranties with  
respect to the contents hereof and specifically disclaims any implied  
warranties of merchantability or fitness for any particular purpose.  
Furthermore, Multi-Tech Systems, Inc. reserves the right to revise this  
publication and to make changes from time to time in the content hereof  
without obligation of Multi-Tech Systems, Inc. to notify any person or  
organization of such revisions or changes.  
Record of Revisions  
Revision  
A
Description  
Manual released. All pages at revision A.  
(7/21/97)  
B
General Update. All pages at revision B.  
(5/28/98)  
Patents  
This Product is covered by one or more of the following U.S. Patent  
Numbers: 5.301.274; 5.309.562; 5.355.365; 5.355.653; 5.452.289;  
5.453.986. Other Patents Pending.  
TRADEMARKS  
Trademark of Multi-Tech Systems, Inc. are as follows: MultiFRAD100, and  
the Multi-Tech logo.  
Windows is a registered trademark of Microsoft.  
Multi-Tech Systems, Inc.  
2205 Woodale Drive  
Mounds View, Minnesota 55112  
(612) 785-3500 or (800) 328-9717  
Fax 612-785-9874  
Tech Support (800) 972-2439  
BBS (612) 785-3702 or (800) 392-2432  
Fax-Back (612) 717-5888  
4
 
Contents  
Chapter 1 - Introduction and Description  
1.1 Introduction ................................................................................. 9  
1.2 About This Manual ................................................................... 10  
1.3 A Typical Application ............................................................... 12  
1.4 FCC Regulations for Telephone Line Interconnection........... 16  
1.5 Canadian Limitations Notice ................................................... 18  
1.6 Specifications ........................................................................... 19  
Chapter 2 - Front and Back Panel Descriptions  
2.1 Introduction ............................................................................... 23  
2.2 Front Panel ............................................................................... 23  
2.3 Back Panel ............................................................................... 25  
2.4 Switch Settings ......................................................................... 26  
2.5 Shunts ....................................................................................... 27  
Chapter 3 - Setup  
3.1 Introduction ............................................................................... 31  
3.2 Unpacking ................................................................................ 31  
3.3 Safety LWarnings ..................................................................... 31  
3.4 Setup......................................................................................... 32  
3.5 V.35 Shunt ................................................................................ 34  
Chapter 4 - Software Loading and Configuration  
4.1 Introduction ............................................................................... 37  
4.2 Loading Software ..................................................................... 37  
4.3 Configuring Your MultiFRAD using Windows ......................... 40  
4.4 Configuring your MultiFRAD using a Dumb Terminal ............ 44  
Chapter 5 - Software Utility Descriptions  
5.1 Introduction ............................................................................... 53  
5.2 MultiFRAD Main Menu ............................................................. 53  
5.2.1 Configuration ................................................................. 54  
5.2.2 Others ............................................................................ 54  
5.2.3 Download ...................................................................... 54  
5.2.4 Exit ................................................................................. 54  
5.2.5 Help ............................................................................... 55  
5.2.6 MultiFRAD Version ....................................................... 55  
5
 
5.3 Data Port Configuration ........................................................... 56  
5.4 Trunk Configuration ................................................................. 62  
5.5 Statistics.................................................................................... 66  
5.6 Diagnostics ............................................................................... 66  
Chapter 6 - ASCII Terminal Menu System  
6.1 Introduction ............................................................................... 71  
6.2 Configurations Menu ............................................................... 71  
6.2.1 Async Data Port Configuration ..................................... 72  
6.2.2 Sync Data Port Configuration ....................................... 75  
6.2.3 Trunk Configuration ...................................................... 77  
6.3 Statistics.................................................................................... 80  
6.4 Reset Options ........................................................................... 82  
6.5 Diagnostic Tests ....................................................................... 82  
Chapter 7 - Service, Warranty and Tech Support  
7.1 Introduction ............................................................................... 87  
7.2 Limited Warranty ...................................................................... 87  
7.3 Tech Support ............................................................................ 87  
7.3.1 Recording MultiFRAD Information ................................ 88  
7.3.2 Service ............................................................................ 89  
7.4 About the Multi-Tech BBS ........................................................ 89  
7.4.1 Logging on to the Multi-Tech BBS ................................ 90  
7.4.2 Downloading a File ....................................................... 90  
7.5 About Compuserve .................................................................. 91  
7.6 About the Internet ..................................................................... 92  
7.7 About the Multi-Tech Fax-Back Service .................................. 92  
7.8 Upgrading the Flash PROM ..................................................... 93  
Appendices  
Appendix A - Cabling Diagrams ..................................................... 97  
 
1
Introduction and  
Description  
 
8
 
1.1  
Introduction  
The Multi-Tech Systems MultiFRAD™ 100-Series, Model number FR111, is a  
one-port Frame Relay Access Device (FRAD) with 56K DSU that  
encapsulates non-packetized data from a serial device into frame relay  
frames and is responsible for framing that data with header and trailer  
information prior to transmission to a frame relay network. The Multi-  
FRAD allows a non-frame relay device to connect to a common carrier  
frame relay network service or private frame relay network. The access  
device is designed with an internal 56K Data Service Unit (DSU) that  
allows a single frame relay permanent virtual circuit (PVC) to be  
connected to a 56K DDS circuit. On the receiving end of the communi-  
cation link, the MultiFRAD serves to strip away the frame relay control  
information in order that the target device is presented with the data  
packaged in its original form.  
The versatility of the MultiFRAD provides for a smooth integration with  
existing equipment; e.g., multiplexers, routers, legacy equipment such  
as cluster controllers, and asynchronous devices such as PCs running  
remote control software. The non-frame relay device connects to the  
data port on the back of the MultiFRAD and is capable of synchronous  
data transmission up to 56K bps or asynchronous data transmission up  
to 57.6K bps. The network connection is provided by the trunk port  
which directly connects to the frame relay network.  
Figure 1-1. MultiFRAD 100-Series  
9
 
1.2  
About This Manual  
This manual describes the MultiFRAD, and tells you how to install and  
configure the unit. The information contained in each chapter is as  
follows:  
Chapter 1 - Introduction and Description  
Chapter 1 introduces the MultiFRAD 100-Series. A typical application  
is presented with a discussion on ordering a frame relay line and how to  
configure a MultiFRAD. A list of relevant specifications are provided at  
the end of the chapter.  
Chapter 2 - Front and Back Panel Descriptions  
Chapter 2 describes the front panel indicators and back panel connec-  
tors. The front panel contains the LEDs for the data and trunk status.  
The back panel provides cable connections to the data port, trunk port,  
and a power connection for an external power supply.  
Chapter 3 - Setup  
Chapter 3 provides unpacking instructions, a setup procedure for  
connecting cables and direction as to when you should configure the  
unit. Also, after the unit is configured and if a V.35 interface is needed  
for the data device, a procedure for changing the shunt to the V.35  
position is provided.  
Chapter 4 - Software Loading and Configuration  
This chapter provides procedures on how to load the software utility and  
configure the unit when a pc with a Windows application is connected to  
the MultiFRAD. If a dumb terminal is connected to the MultiFRAD, the  
unit can still be configured using the ASCII terminal menu system that is  
present in the memory of the unit.  
Chapter 5 - Software Utility Descriptions  
This chapter provides a complete description of the Windows based  
software used on the MultiFRAD 100-Series. From an icon in the  
MultiFRAD program group, the Main menu is displayed. From the Main  
menu, the data Port and trunk can be configured. Trunk statistics,  
diagnostics, and the download feature are also described.  
10  
 
Chapter 6 - ASCII Terminal Menu System  
Chapter 6 provides a description of the ASCII terminal menu system.  
The ASCII terminal menu system is used when a dumb terminal is  
connected to the data port. These menus allow you to configure the  
data port and trunk, view statistics, reset the unit, and enable diagnos-  
tics.  
Chapter 7 - Service, Warranty and Tech Support  
Chapter 5 provides instructions on getting service for your MultiFRAD at  
the factory, a statement of the limited warranty, information about our  
user bulletin board service, and space for recording information about  
your MultiFRAD prior to calling Multi-Tech's Technical Support. The final  
three sections explain how to use our bulletin board service (BBS), and  
get support through CompuServe and the Internet.  
11  
 
1.3  
A Typical Application  
A typical application for a MultiFRAD 100-Series is connecting a single  
non-frame relay device to a frame relay network. The MultiFRAD 100-  
Series is usually used at a remote site where a single DLCI and a single  
device needs to be connected to a frame relay network. A MultiFRAD  
100-Series can connect any existing synchronous or asynchronous  
non-frame relay device to a frame relay network.  
MultiMux  
Data  
Trunk  
LAN 1  
Ethernet Network  
LEVEL  
S
T
Y
N
C
I
N
E
R
(
A
M
L
o
L
d
I
M
M
H
2
m
s
D
)
V
I
O
M
T
N
K
5
6
V
2
9
/
MultiTech  
R
A
N
S
C
T
O
T
R
L
A
L
E
K
Systems  
M
IT  
R
C
V
A
R
M
D
W
N
M
O
D
E
LI  
D
SU  
V
3
3
8
Command Modem  
RCV XMT  
DTR  
Channel Five  
RCV XMT  
Channel Six  
RCV XMT  
Channel Seven Channel Eight  
RCV XMT RCV XMT  
1
2
3
4
CD  
OH  
MultiMux  
External Composite Link  
CD RCV XMT CTS  
Channel one  
RCV XMT  
Channel  
T
w
o
C
h
a
n
n
e
l
T
h
r
e
e
C
h
a
n
n
e
l
F
o
u
r
I
n
t
e
r
n
a
l
C
o
m
p
o
s
i
t
e
L
i
n
k
Statistical Multiplexer  
V
.
3
5
R
C
V
X
M
T
R
C
V
X
M
T
R
C
V
X
M
T
M
M
H
S
2
8
3
4
C
D
R
C
V
X
M
T
C
T
S
2
8
5
.
8
2
1
4
9
.
.
0
2
1
R
9
.
2
1
4
.
4
O
H
T
T
R
M
E
C
D
B
U
P
D
U
C
D
D
R
C
C
V
V
X
M
M
T
T
C
C
T
T
S
S
6
T
S
N
S
O
O
S
V
2
9
/
V
3
3
M
o
d
e
m
C
R
X
Ethernet  
F
LEVEL  
L
S
T
A
S
Y
N
C
I
R
N
(
M
M
m
K
)
E
I
C
E
Channel 2  
T
OC  
N
K
MO  
5
6
K
V
2
9
/
MultiTech  
R
A
N
S
M
IT  
T
R
L
R
C
V
T
E
A
L
A
R
M
Systems  
D
W
N
M
O
D
E
L
D
S
U
V
3
3
8
Command Modem  
RCV XMT  
DTR  
Channel Five  
RCV XMT  
Channel Six  
RCV XMT  
Channel Seven Channel Eight  
RCV XMT RCV XMT  
1
2
3
N
K
4
CD  
OH  
MultiMux  
26  
External Composite Link  
CD RCV XMT CTS  
Channel one  
RCV XMT  
Channel  
T
w
o
C
h
a
n
n
e
l
T
h
r
e
e
C
h
a
n
n
e
l
F
o
u
r
I
n
t
e
r
n
a
l
C
2
o
m
p
4
o
s
i
t
e
L
i
n
k
Statistical Multiplexer  
V
.
3
5
R
C
V
X
M
T
R
C
V
X
M
T
R
C
V
X
M
T
M
M
H
S
2
8
3
4
C
D
R
C
V
X
M
T
C
T
S
2
8
5
.
8
2
1
4
9
.
.
0
2
1
R
9
.
1
4
.
O
H
T
T
R
M
E
C
D
B
U
P
D
U
C
C
D
D
R
C
C
V
V
X
M
M
T
T
C
C
T
T
S
S
6
T
S
N
S
O
O
S
V
2
9
/
V
3
3
M
o
d
e
m
R
X
16  
17  
MultiFRAD 100  
Frame Relay  
Network  
Trunk  
MultiMux  
Channel 1  
Remote Site 2  
27  
®
T1 DSU  
T
ec  
h
Systems  
Trunk  
Data  
MultiFRAD II  
PC  
Host Site  
PC  
MultiFRAD 100  
Remote Site 1  
Figure 1-2. Typical Frame Relay Network  
A MultiFRAD is easily connected to a frame relay network. One Data  
Link Connection Identifier (DLCI) is required and it is provided by your  
local network service provider when you request (subscribe) for a local  
telephone line connection. When your local network service provider  
engineers your connection, a virtual circuit is established between your  
location and the destination of your connection. This virtual circuit is  
called a permanent virtual circuit (PVC).  
1.3.1 Ordering a Frame Relay Line  
Ordering frame relay services from your local telephone company  
involves connecting the physical line, defining the port connection,  
configuring the PVC through the network, and assigning the Data Link  
Connection Identifier (DLCI). The DLCI is a number between 16 and  
1007 that identifies the PVC between your MultiFRAD and the phone  
company's switch. The DLCI is assigned at the same time your local  
service provider defines the permanent virtual circuit (PVC) that is the  
path to your destination. When a PVC is assigned, an average guaran-  
teed throughput is negotiated with the service provider. The guaranteed  
throughput is called committed information rate (CIR) and is based on  
12  
 
your capability to present data to the local telephone switch. Your  
capability to present data is determined by the internal DSU (Data  
Service Unit) that can transfer digital data at a maximum rate of 56,000  
bits-per-second to the network. A general rule of thumb in this scenario  
is to assign a CIR of 32K bps and an excess burst rate (Be) of 24K bps.  
The sum of the CIR and Be can not exceed your capability to present  
data to the network. Finally during subscription, the management type  
is defined by the local frame relay service provider. The management  
type is a mechanism for communicating the status of the PVC and is  
dependent upon which type is running on the telephone switch. Three  
types of management are supported by the MultiFRAD: local manage-  
ment interface (LMI), Annex A, and Annex D.  
1.3.2 How to Configure a MultiFRAD  
Configuring a MultiFRAD is a simple process of defining the data port  
device and the trunk parameters for frame relay. To configure a Multi-  
FRAD, a pc has to be connected to the Data port on the MultiFRAD and  
the MultiFRAD software loaded. To define the data port, the type of  
device that is connected to it has to be defined. If the device is a  
synchronous device such as a multiplexer, then the clocking and speed  
of the device have to be defined in the Data Port Configuration dialog  
box. A couple of other parameters also have to be set in order for the  
multiplexer to communicate with the MultiFRAD.  
If the data device is an asynchronous device, the Asynchronous Mode  
option button changes the dialog box to display the asynchronous  
parameters. The async parameters are the normal baud rate, word  
13  
 
length, parity, stop bits, and flow control. The Async Data Port Configu-  
ration dialog box displays the default parameters that may apply to a  
majority async devices.  
When the data device is defined, then the trunk configuration needs to  
be defined. The trunk configuration is displayed in the Trunk Configura-  
tion dialog box. Most of the trunk information is supplied by your  
network service provider.  
For example, if the MultiFRAD at remote site 2 in our typical Frame  
Relay network in Figure 1-2 is being configured, the DLCI is 26, the  
Access Rate is 56000, and generally a Committed Info Rate of 32000  
with a Excess Burst Rate (Be) of 24000 would allow the multiplexer at  
remote site 2 to communicate with the host site. These parameters can  
be added to the Trunk Configuration dialog box with a Management  
Type defined by your network service provider, lets say for this example  
that it is LMI. The default Management Parameters in the Trunk Configu-  
ration dialog box for the most part should work for this typical applica-  
14  
 
tion. The trunk configuration would be complete by clicking on the Save  
button and returning to the Main menu. In the Main menu, click on the  
download button to transfer the configuration to the MultiFRAD. Within a  
few seconds the new configuration is downloaded to the MultiFRAD and  
it is ready for operation.  
15  
 
1.4 FCC Regulations for Telephone Line Intercon-  
nection  
1. This equipment complies with Part 68 of the FCC rules. On the  
outside surface of this equipment is a label that contains, among other  
information, the FCC registration number and ringer equivalence  
number (REN). If requested, this information must be provided to the  
telephone company.  
2. As indicated below the suitable jack (USOC connecting arrange-  
ment) for this equipment is shown. If applicable, the facility interface codes  
(FIC) and service order codes (SOC) are shown.  
3. The ringer equivalence number (REN) is used to determine the  
quantity of devices which may be connected to the telephone line.  
Excessive RENs on the telephone line may result in the devices not  
ringing in response to an incoming call. In most, but not all areas, the  
sum of the RENs should not exceed five (5.0). To be certain of the  
number of devices that may be connected to the line, as determined by  
the total RENs, contact the telephone company to determine the  
maximum REN for the calling area.  
4. If this equipment causes harm to the telephone network, the tele-  
phone company will notify you in advance. But if advance notice isn’t  
practical, the telephone company will notify the customer as soon as  
possible. Also, you will be advised of your right to file a complaint with  
the FCC if you believe it is necessary.  
5. The telephone company may make changes in its facilities, equip-  
ment, operations, or procedures that could affect the operation of the  
equipment. If this happens, the telephone company will provide ad-  
vance notice in order for you to make necessary modifications in order  
to maintain uninterrupted service.  
6. If trouble is experienced with this equipment (the model of which is  
indicated below) please contact Multi-Tech Systems, Inc. at the address  
shown below for details of how to have repairs made. If the trouble is  
causing harm to the telephone network, the telephone company may  
request you remove the equipment from the network until the problem is  
resolved.  
7. No repairs are to be made by you. Repairs are to be made only by  
Multi-Tech Systems or its licensees. Unauthorized repairs void registra-  
tion and warranty.  
8. This equipment cannot be used on public coin service provided by  
the telephone company. Connection to Party Line Service is subject to  
state tariffs. (Contact the state public utility commission, public service  
16  
 
commission or corporation commission for information.)  
9. If so required, this equipment is hearing aid compatible.  
Manufacturer:  
Multi-Tech Systems, Inc.  
MultiFRAD 100-Series  
AU7USA-24704-XD-N  
N/A  
Model Number:  
FCC Registration Number:  
Ringer Equivalence:  
Modular Jack (USOC)  
Service Center in U.S.A.  
RJ48  
Multi-Tech Systems Inc.  
2205 Woodale Drive  
Mounds View, MN 55112 USA  
(612) 785-3500 or (800) 328-9717  
U.S. Fax (612) 785-9874  
17  
 
1.5  
Canadian Limitations Notice  
Notice: The ringer equivalence number (REN) assigned to each  
terminal device provides an indication of the maximum number of  
terminals allowed to be connected to a telephone interface. The  
termination of a interface may consist of any combination of devices  
subject only to the requirement that the sum of the ringer equivalence  
numbers of all the devices does not exceed 5.  
Notice: The Industry Canada label identifies certificated equipment. This  
certification means that the equipment meets certain telecommunica-  
tions network protective, operational and safety requirements. The  
Industry Canada does not guarantee the equipment will operate to the  
user’s satisfaction.  
Before installing this equipment, users should ensure that it is permis-  
sible to be connected to the facilities of the local telecommunications  
company. The equipment must also be installed using an acceptable  
method of connection. The customer should be aware that compliance  
with the above conditions may not prevent degradation of service in  
some situations.  
Repairs to certified equipment should be made by an authorized  
Canadian maintenance facility designated by the supplier. Any repairs  
or alterations made by the user to this equipment, or equipment  
malfunctions, may give the telecommunications company cause to  
request the user to disconnect the equipment.  
Users should ensure for their own protection that the electrical ground  
connections of the power utility, telephone lines and internal metallic  
water pipe system, if present, are connected together. This precaution  
may be particularly important in rural areas.  
Caution: Users should not attempt to make such connections them-  
selves, but should contact the appropriate electric inspection authority,  
or electrician, as appropriate.  
18  
 
1.6  
Specifications  
Data Port  
• Single data port with synchronous or asynchronous data format  
• Async data rate up to 57.6K bps or sync data rate up to 56K bps  
• RS232C and ITU-T V.35 interface using an adapter cable  
• Internal shunt plugs to configure RS232C or ITU-T V.35 interface  
• Async data format of 5,6,7, or 8 bits; 1, 1½, or 2 stop bits; odd,  
even, or no parity  
• Sync data format is HDLC/SDLC  
• Data port connector is a DB-25 female  
Trunk  
• Single trunk port with synchronous DDS or compatible data format  
• Sync data rate of 56k bps  
• DDS interface with an RJ-48 keyed jack  
• Full duplex over LADS (Local Area Data Set) or two-pair non-  
loaded metallic wire  
Electrical/Physical/Environmental  
• Voltage - 115v AC, 50/60 Hz  
• Power - 2 watts  
• Dimensions - 4.3" W x 1" H x 5.6" L  
- 10.8 cm x 2.5 cm x 14.2 cm  
• Weight - 8 oz. (224 g)  
Temperature - 32° to 120° F (0° to 50° C)  
• Humidity - 20 - 90% non-condensing  
Compatibility  
• Link management via ANSI T1.617 Annex D, ITU-T Q.933 Annex A  
or LMI  
19  
 
20  
 
2
Front and Back  
Panel Descriptions  
21  
 
22  
 
2.1  
Introduction  
This chapter describes the front panel LEDs and back panel connectors.  
The front panel has one row of LEDs for both the data channel and  
trunk status. Two back panel connectors provide the data and trunk  
connections. A circular power connector is provided to connect the  
external power supply.  
2.2  
Front Panel  
The front panel contains two sets of LEDs that provide the status of the  
data and trunk connections. The data LEDs display the activity of the  
data port, if V.35 interface signaling is used, and whether command  
mode is active. The trunk LEDs display status whether the trunk is  
transmitting or receiving frames, link status, and congestion.  
Figure 2-1. Front Panel  
Data  
35  
Lights when the data port is configured for a V.35  
interface. That is, the data shunt is in the V.35 position.  
CM  
Command Mode (CM) LED lights when the Data/  
Command mode switch is in the Command mode  
position and blinks when the unit is in test mode.  
TD  
RD  
Transmit Data (TD) LED blinks when data is being  
transmitted - on for a space and off for a mark.  
Receive Data (RD) LED blinks when data is being  
received - on for a space and off for a mark.  
DSU  
TD  
RD  
Transmit Data (TD) LED blinks when data is being  
transmitted - on for a space and off for a mark.  
Receive Data (RD) LED blinks when data is being  
23  
 
received - on for a space and off for a mark.  
DSU  
NS  
Data Service Unit (DSU) LED lights when the unit is in  
the DSU-only mode.  
The No Signal (NS) LED lights when no signal is  
received from the network or when the signal is too  
weak for normal operation.  
OOS  
CD  
The Out Of Service (OOS) LED lights when an outage  
condition occurs. This happens when there is a failure  
in the digital service that is detected by the network  
and the telco sends a repetitive OOS sequence.  
The Carrier Detect (CD) LED lights when a carrier  
signal is received from the network.  
Trunk  
CN  
LK  
Congestion (CN) LED lights when congestion is  
detected on the trunk.  
Link (LK) LED blinks slowly when there is no link  
management connection with the network. Blinks  
quickly when link management is established with the  
network. Remains solid ON when the network  
indicates the PVC is active.  
CD  
TD  
RD  
Carrier Detect (CD) LED lights when a carrier signal is  
detected from the network.  
Transmit Data (TD) LED blinks when data is being  
transmitted - on for a space and off for a mark.  
Receive Data (RD) LED blinks when data is being  
received - on for a space and off for a mark.  
24  
 
2.3  
Back Panel  
The cable connections for the MultiFRAD are made at the back panel.  
Two cable connections are provided and one power supply connection.  
The Data connector allows the MultiFRAD to be connected to a non-  
frame relay device and the Trunk connector connects to a common  
carrier frame relay network service or private frame relay networks. The  
cable connections are shown in Figure 2-2 and defined in the following  
sections.  
Pow  
e
r
Dat  
a
T
runk  
Figure 2-2. Back Panel  
Power Connector  
The Power connector is used to connect the external wall type trans-  
former power supply to the MultiFRAD. The wall transformer plugs  
directly into an AC outlet.  
Trunk Connector  
The Trunk connector is used to connect the MultiFRAD to a 56K DDS  
circuit that provides the local access to the frame relay service. This  
connector is a RJ48-keyed jack on the back panel of the unit.  
Data Connector  
The Data connector is used to connect the MultiFRAD to a non-frame  
relay device, such as, multiplexers, routers, or legacy equipment such  
as cluster controllers, or an asynchronous device such as a PC running  
remote control software. A second use of this connector is to configure  
the MultiFRAD. The Data connector is a DB-25 female connector  
located on the back panel of the MultiFRAD.  
The Data connector interface can be either an RS-232C or V.35 inter-  
face. When the V.35 interface is used, the data shunt has to be moved  
from the default RS232 position to the V.35 position. Refer to "Shunt" in  
this chapter for changing the data shunt. Refer to Appendix A for  
cabling requirements in V.35 mode.  
25  
 
2.4  
Switch Settings  
The 8-position DIP switch located on the right side of the MultiFRAD  
only uses the first four positions. The DIP switches are shown in Figure  
2-3 and their settings are described in Table 2-1.  
DIP-Switches  
Figure 2-3. Switch Settings  
Table 2-1. Switch Settings  
Switch  
Mode  
Position  
Description  
Data  
1
Cmd/Data UP*  
DOWN  
Command  
DDS  
2
3
Clocking  
UP*  
DOWN  
Internal  
Normal  
Loopback  
FRAD  
Loopback UP*  
DOWN  
4
DSU  
UP  
DOWN*  
DSU  
5-8  
Not Used  
*Factory default setting  
26  
 
2.5  
Shunts  
V.35 signal levels are generally more reliable for high speed data and/  
or longer cable distances. EIA-232D signal levels are intended for data  
rates of 19,200 bps or less and cable lengths of 50 feet or less. For  
higher speeds and/or longer distances, V.35 is generally preferred.  
There are two shunt positions on the printed circuit board that configure  
the data port for either RS232 or V.35 interface. Both DIP sockets for the  
shunts are shown in Figure 2-4.  
V.35 Shunt Position  
RS232 Shunt Position  
Figure 2-4. Shunts  
In Figure 2-3, the shunt is shown in the RS232 (default) position (i.e., in  
the right-hand DIP socket - the one closest to the DIP switches. To  
change the location of the shunt, refer to the V.35 Shunt procedure in  
Chapter 3.  
27  
 
28  
 
3
Setup  
 
30  
 
3.1  
Introduction  
This chapter describes the unpacking of the MultiFRAD, cable connec-  
tions depending on whether EIA-232D or ITU-T V.35 interface signaling  
is used on the data port, and how to configure the unit dependent on  
your site situation. Once the MultiFRAD is configured, then the data port  
can be connected to your data port device.  
3.2  
Unpacking  
The shipping box contains the MultiFRAD, power adapter, and your  
owner's manual. Inspect the contents for signs of any shipping damage.  
If damage is observed, do not power up the unit, contact Multi-Tech's  
Technical Support for advice (refer to Chapter 7 - Warranty). If no  
damage is observed, place the MultiFRAD in its final location and verify  
the signal levels (EIA-232D or ITU-T V.35) for the data port, and connect  
your cables, phone lines, and power supply.  
3.3  
Safety Warnings  
1. Never install telephone wiring during a lightning storm.  
2. Never install telephone jacks in wet locations unless the jack is  
specifically designed for wet locations.  
3. Never touch uninsulated telephone wires or terminals unless the  
telephone line has been disconnected at the network interface.  
4. Use caution when installing or modifying telephone lines.  
5. Avoid using a telephone (other than a cordless type) during an  
electrical storm. There may be a remote risk of electrical shock  
from lightning.  
6. Do not use the telephone to report a gas leak in the vicinity of the  
leak.  
31  
 
3.4  
Setup  
Use the following steps to setup your MultiFRAD. If V.35 electrical  
interface signaling is required on the data port, but a pc with EIA-232D  
signaling is being used to configure the MultiFRAD, the unit has to be  
configured before you change to V.35 signaling. Perform the following  
procedure to connect your cables, configure the unit, and then change  
to V.35 signaling on the data port.  
1. Ensure that the DIP-Switch settings on the side of the unit are set  
for a command mode of operation. Refer to the Switch Settings in  
Chapter 2.  
DIP-Switches  
Figure 3-1. DIP-Switch Settings  
2. Connect the external wall transformer power supply to the Multi-  
FRAD and plug it into a live AC outlet. The MultiFRAD does not  
have a power switch. When power is applied to the unit, the front  
panel LEDs will light.  
Trunk  
Data  
Power  
Figure 3-2. Power Connection  
3. Connect a pc running Windows® to the Data connector on the  
back of the MultiFRAD. Use an appropriate EIA-232D cable.  
Refer to Appendix A for EIA-232D cable details.  
Data  
Power  
Trunk  
PC Serial Cable  
Figure 3-3. Data Connection  
32  
 
4. Connect an RJ48 phone cable to the Trunk connector on the back  
of the MultiFRAD. Connect the other end of the phone cable to the  
local access line jack.  
Trunk  
Data  
Power  
Figure 3-4. Trunk Connection  
5. The MultiFRAD can be configured in two ways: If a pc running a  
Windows software is being used to configure the unit, refer to the  
Software Loading procedure in Chapter 4.  
If a terminal running a communications software is being used to  
configure the unit, refer to Configuring your MultiFRAD using a  
dumb terminal in Chapter 5.  
6. Once the MultiFRAD is configured for your application, you can  
disconnect the pc and connect your data port device. If the data  
port device contains an EIA-232D interface, the same serial cable  
can be used. If the data port device contains a V.35 interface, the  
data port shunt must be moved to the V.35 position and a V.35  
adapter cable must be connected to the data port connector. Refer  
to Section 3.5 for procedures on moving the shunt to the V.35  
position. Refer to Appendix A for cable details.  
7. Place the Command Mode switch (Switch 1) on the side of the  
MultiFRAD in the UP position for the data mode operation.  
33  
 
3.5  
V.35 Shunt  
Either EIA-232D or ITU-T V.35 electrical signal interface can be selected  
on the data port. Units are shipped with EIA-232D signal levels se-  
lected. Use the following procedure to select V.35.  
CAUTION  
This procedure requires opening the unit. Like most  
products of this type, this product contains components  
that are sensitive to static and static discharge. Please  
use your best efforts to avoid static discharge when  
contacting the components inside this unit.  
WARNING:  
Always disconnect the power cord before opening  
the enclosure to avoid any chance of electric shock.  
1. Unplug the power cord.  
2. The enclosure consists of two halves. Using a Phillips screwdriver,  
remove the two screws from the bottom of the unit. Remove the  
top half.  
3. Pry the data port shunt out of its RS232 socket and insert it into the  
V.35 socket.  
V.35 Shunt Position  
RS232 Shunt Position  
Figure 3-5. Shunts  
4. Carefully reassemble the unit, making sure that no foreign objects  
are accidentally left inside.  
6. The data port is now configured with V.35 signal levels. The cable  
pin designations are shown in Appendix A. To connect to a device  
equipped with a V.35 34-pin connector, you must obtain an  
adapter cable. Using the signal pin designations in Appendix A,  
you may make or order a cable from most any cable vendor.  
34  
 
4
Software Loading  
and Configuration  
35  
 
36  
 
4.1  
Introduction  
This chapter covers the loading of the software utility and then the  
configuration of the unit from either a Windows based pc or a dumb  
terminal. When a Windows based pc is used, the software utility is  
loaded using the procedures in section 4.2 and then the unit is config-  
ured using the procedures in section 4.3. If a dumb terminal is used, the  
MulitFRAD 100 can be configured using the ASCII terminal menu  
system present in memory of the unit.  
4.2  
Loading Software  
1
2
Turn on your PC connected to the Data Port of your MultiFRAD  
and run Windows®.  
Create a backup copy of your MultiFRAD software diskette before  
you install the software. Store the master diskette in a safe place  
and install the MultiFRAD software using the backup copy.  
3
4
5
6
Insert the backup disk for the MultiFRAD into the floppy drive.  
Click on the File Menu in your Program Manager.  
Click on Run. The Run dialog box is displayed.  
Type a:\install or b:\install (depending on the location of your  
floppy disk drive) in the Command Line field, and then click on  
OK.  
7
The MultiFRAD 100 - Select Directories dialog box is displayed.  
If you are installing the software from drive A and your Destina-  
tion Directory is the default directory, click on OK to continue  
8
The Installing MultiFRAD dialog box is displayed.  
37  
 
Click on Install to continue installation, at any time you may click  
on Abort if you wish to cancel the install immediately.  
9
The Expanding/Copying Files From: dialog box is displayed. You  
can view the progress of the installation from this dialog box. You  
can click on Abort at any time to cancel the install.  
11 The MultiFRAD 100 Installation dialog box asks "Please select a  
communication port for the setup utility to use" dialog box is  
displayed. In other words, select which COM port on your PC that  
is connected to the Command Port of the MultiFRAD.  
38  
 
Select the COM port (COM1,COM2,COM3, or COM4) for the setup  
utility. The default port is COM1. Click on OK when you are  
satisfied with your selection.  
12 When the setup installation is successful, a system message is  
displayed stating "MultiFRAD 100 Installation Successful. Click  
on OK to continue.  
13 Your are returned to the Program Manager where the MultiFRAD  
program group and icons are created.  
This completes the software loading. Now, proceed to configur-  
ing your MultiFRAD.  
39  
 
4.3  
Configuring Your MultiFRAD using Windows  
Configuration of your MultiFRAD using Windows starts after the soft-  
ware is loaded and program group is displayed in the Program Man-  
ager.  
1
Double click on the MultiFRAD 100 Configuration icon.  
2
When the MultiFRAD 100 dialog box is displayed, click on the  
Data Port button to display the Data Port Configuration dialog  
box.  
3
The Data Port Configuration dialog box is displayed with the  
Mode set to Asynchronous. If your data device is an Asynchro-  
nous device, refer to the User documentation to set the async  
parameters that meet the conditions of your installation.  
40  
 
If your data device is a synchronous device, click on the Syn-  
chronous option button and the parameters for the synchronous  
mode are displayed. Refer to the User documentation to set the  
sync parameters that meet the conditions of your installation.  
4
5
When you are satisfied with your selections, click on the Save  
button to save your new parameters. Then click on the OK button  
to return to the main menu.  
From the Main menu, click on the Trunk button to display the  
Trunk Configuration dialog box.  
41  
 
6
7
Click on the DLCI numeric dialog box. Enter the DLCI number  
that was provided by your service provider at subscription time.  
To change the DLCI, click on the DLCI numeric dialog box and  
back space through the default number and then enter your DLCI.  
Click on the Management type option button supported by your  
Frame Relay network. The Management type is supplied by your  
service provider at subscription time.  
For most applications, the default Management Parameters  
should be adequate.  
Polling Interval is the number of seconds for a polling cycle (i.e.,  
the time period between each status enquiry message sent from  
the MultiFRAD).  
Full Status Counter displays a number between 1 and 255 that is  
the number of polling cycles (minus one) before a full status is  
requested from the network.  
Error Threshold displays a number between 1 and 10 that is less  
than or equal to the Monitored Event count.  
Monitored Event displays a number that is between 1 and 10 that  
is greater than or equal to the Error Threshold.  
8
9
Click on the Committed Info Rate numeric box and enter the CIR  
value provided by your service provider at subscription time.  
Click on the Excess Burst Rate (Be) numeric box and enter the  
Be value provided by your service provider at subscription time.  
10 The Back to Back check box should normally remain unchecked.  
11 Click on the Encapsulation Type you need. Mux Mode encapsu-  
lation can be used only if the FRAD at the other end of the PVC is  
42  
 
another MultiFRAD 100. Raw Mode encapsulation can be used  
for any type of FRAD at the other end.  
12 Click on the OK button to return to the Main menu.  
13 Click on the Download button to write the new configuration to  
the MultiFRAD.  
14 The Configuration dialog box is displayed.  
The Configuration downloaded successfully. Reset the unit for  
configuration to take effect and put dip switch number 1 in the up  
position. Click on OK to proceed.  
15 You are returned to your Program Manager where the MultiFRAD  
100 Program Group and Program Item (the Windows icons) have  
been created.  
Your MultiFRAD 100 is fully operational at this time.  
43  
 
4.4  
Configuring your MultiFRAD using a Dumb  
Terminal  
To configure your MultiFRAD, power up a terminal or pc running  
communications software and hit the ENTER key. The Main menu  
appears on your screen, configure the data port for sync or async mode  
of operation and the trunk for the frame relay parameters. The Multi-  
FRAD configuration is contained in the following procedure.  
1
Apply power to your terminal or pc. After the terminal or pc boots  
up, run the communications software. Setup your communica-  
tions software for a speed between 2400 and 115.2K bps, 8-bits,  
no parity, and 1-stop bit. Press the ENTER key to display the  
MultiFRAD Main Menu.  
2
Enter option 1 and press the ENTER key to display the Configura-  
tion menu.  
Configurations  
1 - Data Port Configuration  
2 - Trunk Configuration  
3 - Factory Default Configuration Options  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection: _  
3
If your Data port is being setup for Async mode of operation,  
proceed to step 4 to configure your data port.  
If your Data port is being setup for a sync mode of operation,  
enter option 1 in the Configuration menu and press ENTER. Enter  
1 again and the Data Port Async/Sync submenu is displayed.  
Enter option 2 for Sync mode of operation. Then proceed to step  
5 to configure your data port.  
44  
 
4
If the data port is being setup for Async mode of operation and a  
port speed of 57.6K, initially the data port does not have to be  
changed, proceed to step 6 to configuring the Trunk.  
Data Port Configuration  
1 - Async/Sync:  
2 - Speed:  
3 - Word Length:  
4 - Stop Bits:  
Async  
57600  
8
1
5 - Parity:  
None  
CTS  
Off  
Off  
Off  
Off  
Off  
6 - Flow Control:  
7 - Enq/Ack Flow Control:  
8 - Echo:  
9 - Pacing:  
10 - EIA Pass Through:  
11 - Pass Xon:  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection : _  
If the data port configuration needs to be changed, enter the  
option number to be changed and a submenu is displayed.  
Change the option to meet the conditions of your installation.  
When the data port is configured to meet your site requirements,  
proceed to step 6 to configure the Trunk.  
5
Change the Sync Data Port Configuration to meet the conditions  
of your installation by selecting the option needing change and a  
submenu is displayed with your selections.  
Data Port Configuration  
1 - Async/Sync:  
2 - Speed:  
Sync  
57600  
Flags  
NRZ  
All 1s  
Off  
3 - Idle Condition:  
4 - NRZ/NRZI Encoding:  
5 - CRC Preset:  
6 - Inter-frame Timer:  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection : _  
When the Sync Data Port is configured to meet your site require-  
ments, enter the letter S and press ENTER to store all configura-  
tions. Then enter the letter P and press ENTER to return to the  
Configuration menu.  
45  
 
6
From the Configuration menu, enter 2 and press ENTER. The  
Trunk Configuration menu is displayed.  
T
r
u
n
k
C
o
n
f
i
g
u
r
a
t
i
o
a
n
t
1
2
3
4
5
6
7
8
9
-
-
-
-
-
-
-
A
c
T
a
L
o
x
a
c
e
s
s
i
r
a
t
e
:
5
F
O
1
6
o
f
0
0
0
R
B
D
C
E
M
S
c
S
g
n
a
l
S
k
t
u
s
:
l
l
o
w
s
i
n
p
u
t
f
r
o
m
D
T
E
k
I
t
o
B
a
c
:
f
C
m
c
:
6
2
4
m
i
t
t
e
d
u
I
n
t
f
o
R
t
a
t
e
(
C
e
I
R
)
:
3
K
K
e
s
s
B
r
s
t
R
a
e
(
B
)
:
2
n
a
g
e
m
e
n
t
y
p
e :  
A n n e x  
A
-
P o l l i n g I n t e r v a l :  
1 0 S e c  
-
F u l l S t a t u s C o u n t e r :  
6
1 0 - E r r o r T h r e s h o l d :  
3
11 - M o n i t o r e d E v e n t C o u n t :  
1 2 - E n c a p s u l a t i o n M o d e :  
4
M u x  
S
M
P
-
S t o r e A l l C o n f i g u r a t i o n s  
M a i n M e n u  
-
-
P r e v i o u s M e n u  
S e l e c t i o n  
:
_
In the Trunk Configuration menu, the Access rate option (1)  
displays the data rate of the trunk. This rate can not be changed.  
Option 2 should remain in the default condition (Follows input pin  
from DTE) when used in a frame relay network. Option 3, the  
Back to Back option should normally remain off. Options 4 thru 6  
are supplied by your service provider at the time the trunk was  
provisioned. These values have to be the same as the provi-  
sioned values. Options 8 thru 11 modify the management  
protocol and for the most part should remain unchanged. Option  
12 Encapsulation Mode depends on the type of device at the  
other end of the frame relay network. If a MultiFRAD is at the  
other end of the network, then the Mux mode needs to be  
selected. If a non-MultiFRAD 100 is at the other end of the  
network, then Raw mode needs to be selected.  
7
To enter the DLCI for your trunk, enter 4 and press ENTER. A DLCI  
submenu is displayed.  
Enter the DLCI(Data Link Connection Identifier).  
Valid values are between 0016 to 1007.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
46  
 
Enter the number that corresponds to the DLCI for your trunk. A  
two-digit number can be entered and the zeros will proceed the  
digits. The DLCI is supplied by your network service provider at  
the time the trunk was provisioned.  
When you have entered your DLCI, the Trunk Configuration menu  
is displayed.  
8
From the Trunk Configuration menu, enter option 5 Committed  
Info Rate (CIR) and the CIR menu is displayed.  
Enter the CIR (Committed Information Rate), in  
units of 1000 (1K). Valid values are between 0K  
and 128K. The CIR should be equal to or less  
than the Trunk access rate.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter the number that corresponds to the CIR in units of 1K for  
your trunk. The CIR range is from 0 to 128K and should be equal  
to or less than the trunk access rate which can not exceed 56K.  
The CIR is supplied by your network service provider at the time  
the trunk was provisioned.  
When you have entered your CIR, the Trunk Configuration menu  
is displayed.  
9
From the Trunk Configuration menu, enter option 6 Excess Burst  
Rate (Be) and the Be menu is displayed.  
Enter the Be (excess Burst Rate), in units of 1000  
(1K). Valid values are between 0K and 128K. The  
sum of Be + CIR should be equal to or less than  
the Trunk access rate.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter the number that corresponds to the Be in units of 1K for  
your trunk. The Be range is from 0 to 128K and the sum of Be  
plus CIR should be equal to or less than the trunk access rate.  
47  
 
The Be is supplied by your network service provider at the time  
the trunk was provisioned.  
When you have entered your Be, the Trunk Configuration menu is  
displayed.  
10 From the Trunk Configuration menu, enter option 7 Management  
Type and the Management Type menu is displayed.  
Management Type  
1 - Annex D (ANSI T1.617)  
2 - LMI  
3 - Annex A (ITU-T Q.933)  
P - Previous Menu  
Selection : _  
Enter the number that corresponds to the Management Type for  
your trunk. The Management Type is supplied by your network  
service provider at the time the trunk was provisioned.  
Options 8 thru 11 modify the management protocol between the  
MultiFRAD and the network switch. For most applications, the  
default values should be adequate. If you do not need to change  
any of them, proceed to step 15.  
11 From the Trunk Configuration menu, enter option 8 Polling  
Interval and the Polling Interval menu is displayed.  
Enter the Polling Interval, in units of seconds.  
Valid values are between 5 and 30 seconds.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter the number of seconds for a polling cycle (i.e., the time  
period between each status enquiry message sent from the  
MultiFRAD).  
12 From the Trunk Configuration menu, enter option 9 Full Status  
Counter and the Full Status Counter menu is displayed.  
48  
 
Enter the Full Status Counter.  
Valid values are between 1 and 255.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter the number between 1 and 255 that is going to be the  
number of polling cycles (minus one) before a full status is  
requested from the network.  
13 From the Trunk Configuration menu, enter option 10 Error  
Threshold and the Error Threshold menu is displayed.  
Enter the Error Threshold.  
Valid values are between 1 and 10. The Error  
Threshold must be less than or equal to the  
Monitored Event Counter.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter a number that is less than or equal to the Monitored Event  
Count.  
14 From the Trunk Configuration menu, enter option 11 Monitored  
Event Count and the Monitored Event Count menu is displayed.  
Enter the Monitored Event Count.  
Valid values are between 1 and 10. The Monitored  
Event Count must be greater than or equal to the  
Error Threshold.  
x - Enter Number, or  
P - Previous Menu  
Selection : _  
Enter a number between 1 and 10 that is greater than or equal to  
the Error Threshold.  
49  
 
15 Enter the letter S and press ENTER to store all configurations.  
Then enter the letter M and press ENTER to return to the Main  
Menu. Enter 5 to Exit Command Mode.  
16 Place the Command Mode switch (Switch 1) on the side of the  
MultiFRAD in the UP position and return to step 6 in the Setup  
procedure in Chapter 3.  
 
5
Software Utility  
Descriptions  
 
52  
 
5.1  
Introduction  
This chapter describes the MultiFRAD software which is designed for  
the Microsoft® Windows® environment. The MultiFRAD 100 Program  
Group has three icons that allow you to launch the software, download  
a firmware update, and configure the console pc port in order to  
communicate with the MultiFRAD.  
The MultiFRAD 100 Configuration icon allows you to configure the data  
port for either a synchronous or asynchronous device, configure the  
trunk for a frame relay network, view statistics of the data port, perform  
diagnostic test of the unit, and download a new configuration to the unit.  
The Download Firmware allows new operating code (firmware) to be  
transferred to the MultiFRAD. The Configuration Port Setup icon  
establishes the parameters for which the console pc communicates with  
the MultiFRAD.  
You may also start the MultiFRAD 100 Configuration from the File  
Manager by selecting the unofrad directory and double clicking on the  
unofrad.exe program in the file list.  
You may also run MultiFRAD 100 Configuration from either the Program  
Manager or the File Manager by clicking on the Run command in the  
File Menu, then typing: C:\unofrad\unofrad.exe in the Command Line  
field.  
5.2  
MultiFRAD Main Menu  
The MultiFRAD 100 Main menu organizes your configuration process  
into the Data Port and Trunk configurations, allows you to view statistics,  
initiate Diagnostics, download a new configuration, exit the application,  
and view help screens.  
The following sections describe each button in the main menu and each  
field and button in each dialog box.  
53  
 
5.2.1 Configuration  
Data Port  
This button allows you configure the data port for either synchronous or  
asynchronous mode of operation.  
Trunk  
This button lets you define the frame relay parameters.  
5.2.2 Others  
Statistics  
This button allows you to view statistics of the trunk port.  
Diagnostics  
This button allows you to run two loopback tests, a memory test, and watch  
dog test.  
5.2.3 Download  
You can update the MultiFRAD setup on the target. This will bring the  
MultiFRAD down for updating the setup. Then, reboot the MultiFRAD.  
5.2.4 Exit  
This will end your MultiFRAD session and return you to the Program  
Manager.  
54  
 
5.2.5 Help  
A thorough On-line Help system is provided with abbreviated informa-  
tion on the dialog boxes and the buttons within a dialog box.  
5.2.6 MultiFRAD Version  
The current version number of the MultiFRAD firmware is displayed in  
this field.  
55  
 
5.3  
Data Port Configuration  
This dialog box allows you to configure the data port. You will be able to  
set the parameters required for the successful operation of the port.  
Mode Asynchronous/Synchronous  
This allows you to set synchronous or asynchronous parameters  
required for transferring data between the MultiFRAD and the data port  
device. The data port can operate either in Asynchronous (UART) mode  
or Synchronous (HDLC) mode. Choose the Mode option that meets  
your site requirements. Both data port modes are discussed in the  
following sections.  
Sync Mode Parameters  
The following parameters are modifiable when the device connected to the  
data port connector on the back of the MultiFRAD 100-Series is a synchro-  
nous device. To change a parameter, click on the option button to be  
activated. To change a parameter using a drop down menu, click on the  
drop down arrow and a drop down menu displays the new parameters.  
Click on the desired parameter.  
Speed  
TheSpeed parameter needs to be set to match the speed of the sync device.  
When the data port is connected to a synchronous device, the baud rate is  
from 300 bps to 56K bps. The default port speed is 56K bps.  
56  
 
Note: The MultiFRAD always provides the clocking signal to the sync  
device. The MultiFRAD 100's data port can not be set to external clocking,  
it is always internal clocking.  
Between Frames  
The Between Frames parameter must be set to match the idle condition of  
the synchronous device connected to the data port. The Between Frames  
determine what happens when the synchronous data line is idle (i.e., no  
data frames are being transmitted). The default condition is to continuously  
send SDLC flags (Flags). The other condition is the mark state (Mark). The  
transmit LED will be off during idle time if the synchronous device is in the  
mark state during idle conditions.  
Encoding Scheme  
The Encoding Scheme parameter refers to the fact that synchronous data  
can be encoded by using either NRZ (Non-Return to Zero) or NRZI (Non-  
Return to Zero Inverted) method. This parameter must match the synchro-  
nous device’s encoding. The default is NRZ. With NRZ encoding, the data  
is represented normally. With NRZI encoding, a logical one is represented  
by no transmission and a zero is represented by a transition at the beginning  
of the bit. Most synchronous devices can be configured for either NRZ or  
NRZI. Ifasynchronousdeviceisnotconfigurable, itmostlikelyissettoNRZ.  
Refer to the device’s user documentation for the encoding method.  
InterFrame Timer (in mS)  
The InterFrame Timer parameter can be changed to make the MultiFRAD  
wait a specified length of time between frames. You can choose Off and  
delay times of 2,5,10 and 15 milliseconds. A typical use for this parameter  
is to simulate transmission delays encountered with equipment that toggles  
hardware signals after transmission of each frame, like PC cards used to  
connect to legacy systems. The following options can be specified for the  
timer: Off, 2mS, 5mS, 10mS, and 15mS. The default is off.  
57  
 
CRC Preset  
The CRC Preset parameter allows the user to specify whether the polyno-  
mial used to calculate the CRC for each frame is preset to all 1s or all 0s.  
This option must match the synchronous device’s CRC-preset setting. The  
default is All 1s.  
Async Mode Parameters  
Following Parameters are modifiable when the device connected to the  
data connector on the back of the MultiFRAD 100-Series is an asynchro-  
nous device. To change a parameter using a drop down menu, click on the  
drop down arrow and a drop down menu displays the new parameters.  
Click on the desired parameter. To change an option parameter, click on  
the option box. An "x" appears in the option box if the option is active.  
Baud Rate  
The Baud Rate parameter needs to be set to match the speed of the async  
device. The baud rate ranges from 300 bps to 57.6K bps. The default port  
speed is 19.2k bps.  
Word Length  
The Word Length parameter sets the number of bits in a word. The word  
length range is 5 to 8 bits. The default is 8 bits.  
58  
 
Parity  
The Parity parameter sets parity for odd, even or none. Under normal  
conditions, parity is set to none. The default is none.  
Stop Bits  
The Stop Bits parameter sets the number of stop bits. The number of stop  
bits can be 1, 1.5, or 2. The default is 1 bit.  
Flow Control  
The Flow Control parameter allows for two types of flow control: the  
software-based XON/XOFF and the hardware-based Clear to Send (CTS).  
The default is CTS. Flow control is the means by which data flow from the  
device into the MultiFRAD is controlled. Flow control is necessary when the  
data handling capacity of the data port cannot keep up with the volume of  
data sent to it. When the data device controls data flow to itself, it is called  
pacing (see Pacing). The combination of flow control from the port device  
and pacing to the data device is how data transfers are regulated so that  
no data is lost.  
CHANNEL DEVICE-  
INITIATED PACING  
MultiFRAD-INITIATED  
FLOW CONTROL  
DATA  
DATA  
Channel  
Device  
Channel  
Device  
MultiFRAD  
MultiFRAD  
Flow control stops the input  
of data to the MultiFRAD  
Pacing stops the output of  
data from the MultiFRAD  
Pacing  
The Pacing parameter controls the data flow to the data device. Pacing is  
necessary when the flow of data to a device operating on the data port is  
more than it can process. If the device cannot process the volume of data  
sent to it, then the pacing option should be turned on. The pacing method  
used is determined by the type of flow control. The default condition is for  
this option to be turned off.  
59  
 
Pass Xon  
The Pass Xon parameter enables the XON/XOFF flow control signals to be  
passed on to the data device. This option has to be used in conjunction with  
the software-based XON/XOFF flow control option. The default condition is  
for this option to be turned off, and normally it should remain off.  
Echo  
The Echo parameter enables data entered on the data device keyboard to  
be returned to the device's monitor. The purpose of this option is so that an  
operator will not experience undue delays in seeing entered data appear  
on their monitor. The default condition for the echo option is off.  
EIA Pass Through  
The EIA Pass Through parameter allows the data device to receive EIA  
control signals through the MultiFRAD. Since, in normal interactive oper-  
ation, the existence of a MultiFRAD should be transparent to the user, the  
EIA pass through option allows a terminal to operate as if it were connected  
directly to a communications line and not through a MultiFRAD. This is done  
by allowing selected pins (signals) on one MultiFRAD to be passed through  
to selected pins on a remote MultiFRAD. The default condition is for this  
option to be turned off. The following diagram shows how the EIA pass  
through option routes the selected signals:  
MultiFRAD  
B
MultiFRAD  
A
IN 4  
IN 20  
8 OUT  
6 OUT  
Trunk Facility  
OUT 8  
OUT 6  
4 IN  
20 IN  
60  
 
ENQ/ACK  
The Enq/Ack parameter is a special flow control protocol used in Hewlett  
Packard computer systems. This option is sometimes referred to as  
Enquire/Acknowledge flow control because it’s based on the computer  
sending an enquiry (ENQ) and then expecting an acknowledgment (ACK).  
61  
 
5.4  
Trunk Configuration  
This dialog box allows you to configure the trunk. You will be able to set  
the parameters required for the successful operation of the trunk.  
Frame Relay is a multiplexing protocol designed to operate over  
transmission facilities that are virtually error free. In Frame Relay,  
frames are routed through the network on the basis of an attached label  
called a Data Link Connection Identifier (DLCI). Frame Relay combines  
the bandwidth efficiency of packet switching with end-to-end protocol  
transparency, increased speed and performance.  
Data Link Connection Identifier (DLCI)  
The DLCI is the identification of a particular logical link in the Frame Relay  
network and has local significance only. The DLCI is assigned by the frame  
relay service provider for the PVC (Permanent Virtual Circuit) that is on your  
access circuit. As the logical link traverses the Frame Relay network, input  
DLCI will be mapped to an output DLCI at every node. Access DLCIs for  
permanent logical links are assigned at subscription time. Trunk DLCIs are  
allocated dynamically. The valid value for a DLCI ranges from 16 to 1007  
with a default of 16.  
Management Type  
The Management Interface defines a set of procedures and messages to  
manage a PVC and the physical link at the user network interface. Three  
management types are used: Local Management Interface (LMI), Annex A,  
or Annex D. The management type is determined by the network service  
provider at subscription time.  
62  
 
LMI describes a protocol and associated procedures operating on the local  
interface between the user and the network. It notifies the user of the  
addition, deletion, and presence of the PVC in the network. It also notifies  
the user of the end-to-end availability or unavailability of a PVC. Basic LMI  
protocol is based on a synchronous polling scheme where the user polls  
the network to obtain status information on the PVCs configured on the  
interface. LMI simply augments the ANSI/CCITT standard Frame Relay  
protocol and in no way interferes with the normal operation of user PVCs  
on the interface.  
Annex D provides additional procedures for permanent virtual connections  
using unnumbered information frames. Annex D describes the means for  
notification of outage of a permanent virtual connection and recovery from  
such a condition. This follows the ANSI T1.617 standards.  
Annex A provides additional procedures for permanent virtual connections  
using unnumbered information frames. Annex A describes the means for  
notification of outage of a permanent virtual connection and recovery from  
such a condition. This follows the ITU-T Q.933 standard  
Encapsulation Type  
The Encapsulation Type depends on the type of device that is connected  
at the other end of the trunk. If another MultiFRAD 100 is connected at the  
other end of the trunk, then the Mux mode is used. If a non-MultiFRAD 100  
is at the other end of the trunk, then the Raw mode is used.  
Management Parameters  
PollingInterval  
The Polling Interval defines a time period in which a status enquiry message  
is sent from the MultiFRAD to the network. The Status Enquiry message  
requests the status of the PVC(s) or verification of the status of a physical  
link. WhentheStatusEnquirymessageissentbytheMultiFRAD, thePolling  
Interval is restarted. The network responds with a status message that  
reports the status of the PVC or verifies the integrity of the physical link. The  
polling interval is 5 to 30 seconds with a default of 10 seconds.  
63  
 
Full Status Counter  
The Full Status Counter determines how may Polling Intervals take place  
before a full status is requested from the network. A full status enquiry  
message is sent from the MultiFRAD to the network requesting a status  
report of the PVC on the physical link. The Full Status Counter can range  
from 1 to 255, with a default of 6.  
Error Threshold  
The Error Threshold is used to indicate the threshold number of errors  
occurring during a full cycle of the Monitored Event. After each full cycle of  
the Monitored Event Counter, if the actual number of errors equals or  
exceeds the error threshold, the trunk status is brought down and no data  
may be sent. The error count is reset at the beginning of each cycle of the  
Monitored Event Counter. The Error Threshold Count can range from 1 to  
10 with a default of 3 and should be less than or equal to the Monitored Event  
Counter.  
Monitored Event  
The Monitored Event determines the number of Polling Intervals that have  
to take place before the User Network Interface is operational. It is also used  
with the error threshold count to determine if the trunk should be brought  
down. The range of this counter is from 1 to 10 events with a default of 4  
events  
Committed Info Rate (CIR)  
The Committed Info Rate (CIR) determines the data transfer rate at which  
the network is committed to handle under normal conditions. This rate is  
the average over a minimum increment of time. The CIR may be less than  
or equal to the Access Rate. When the CIR is exceeded, but the data rate  
is below the Excess Burst Rate (Be), there is a possibility that data may be  
discarded. When the Be is exceeded, data will most likely be discarded.  
The default CIR is 32K.  
64  
 
Back to Back  
The Back to Back is used to test the port by connecting two MultiFRADs  
together without a frame relay network in between them. Back-to-back  
mode still requires the use of DSU/CSUs, but they should not be connected  
over the frame relay network. The options are On and Off with a default of  
Off.  
Back-to-back mode is useful when two MultiFRADs are at the same location  
and they are connected via DSUs for testing. Back-to-back mode can also  
be used to connect two MultiFRADs over a private leased line.  
Excess Burst Rate (Be)  
The Excess Burst Rate (Be) defines the maximum allowable data transfer  
rate the MultiFRAD can exceed the Committed Info Rate (CIR) during a time  
interval. TheBeisthemaximumadditionaldatarateatwhichtheMultiFRAD  
can present to the network during a time interval. The default Be is 24K.  
65  
 
5.5  
Statistics  
This dialog box allows you to view status of the trunk. Its possible to  
view signal status and other characteristics like data frames transmitted  
or received, status of enquiries transmitted and messages received and  
the status of the messages received.  
If you want to clear the statistics so that you can have fresh statistics,  
then you should click on the clear button.  
5.6  
Diagnostics  
The MultiFRAD Diagnostics dialog box allows you to run two loopback  
tests, a memory test, and watch dog test. The Diagnostics dialog box is  
displayed by clicking on the Diagnostic button in the MultiFRAD dialog  
box.  
66  
 
Loop Tests  
The loop tests provide a short and long loop test. The short loop test is the  
data port loopback test which loops back the data from the data port to the  
sending device (DTE). The long loop test is the trunk loopback test which  
again receives data from the DTE device and loops it back from the internal  
DSU.  
The data port loopback test has two modes which depend on the device  
connected to the data port. If the data port device is an async device, then  
the Command Mode switch (DIP-Switch position 1) can be in either position  
in order for the data to be looped back to the sending (DTE) device. If the  
data port device is a sync device, the Command Mode switch must be in the  
up position (Data mode) in order for the device to receive the looped back  
data.  
The trunk loopback test requires that DIP-Switch position 3 (Loopback Test  
Mode) be in the DOWN position in order for the internal DSU to loop back  
the data received from the DTE device.  
Other Tests  
The memory test checks the on-board memory. A warning will be displayed  
that "The unit will be reset now and the factory defaults will be restored.  
The watch dog test will reset the unit. A "Warning: This watchdog test will  
reset the unit. Do you wish to continue?" A brief message will be displayed  
stating that the watch dog test passed.  
67  
 
 
6
ASCII Terminal  
Menu System  
 
70  
 
6.1  
Introduction  
The menu system for the MultiFRAD provides a set of user-friendly  
configuration menus that are accessible from a main menu. The Main  
Menu contains five options that allow you to configure your MultiFRAD;  
display statistics; reset the unit or data port; run diagnostic tests, and  
exit the command mode.  
To select one of the options from the Main Menu, enter the number  
corresponding to the option and press ENTER. A submenu is displayed  
that allows you to configure your MultiFRAD, display statistics, or run  
one of many diagnostics tests.  
6.2  
Configurations Menu  
From the Configurations menu you can configure the data port or trunk,  
restore factory defaults; store all current configurations; or return to the  
Main Menu.  
Configurations  
1 - Data Port Configuration  
2 - Trunk Configuration  
3 - Factory Default Configuration Options  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection: _  
To configure the data port or trunk, enter the corresponding option  
number and press ENTER. To change to factory defaults, enter number  
3 and press enter. You can set factory defaults for the entire unit or for  
either the data port or trunk. Select the option you wish to change, and  
71  
 
a message will appear on your screen saying to wait for 3 seconds.  
Then press ENTER to return to the Main Menu. To store the current  
configuration, enter S and press ENTER. To return to the Main Menu,  
enter M and press ENTER.  
6.2.1 Async Data Port Configuration  
The Async Data Port Configuration menu allows you to configure the  
data channel for either asynchronous or synchronous operation,  
depending on the type of device connected to the data port. If the port is  
configured for synchronous operation, refer to Sync Data Port Configu-  
ration.  
When the port is configured for asynchronous operation, options such  
as speed, flow control, and pacing may need to be changed. The  
following Data Port Configuration menu displays the default parameters  
for async mode of operation:  
Data Port Configuration  
1 - Async/Sync:  
2 - Speed:  
3 - Word Length:  
4 - Stop Bits:  
Async  
57600  
8
1
5 - Parity:  
None  
CTS  
Off  
Off  
Off  
Off  
Off  
6 - Flow Control:  
7 - Enq/Ack Flow Control:  
8 - Echo:  
9 - Pacing:  
10 - EIA Pass Through:  
11 - Pass Xon:  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection : _  
The Async/Sync option configures the port for either asynchronous or  
synchronous operation. When an asynchronous device such as a PC or  
a host computer is connected to the port, the data port needs to be  
configured for asynchronous operation. The default for this option is  
Async.  
The Speed option needs to be set to match the speed of the async  
device. When the data port is connected to an asynchronous device,  
the baud rate can range from 300 bps to 57.6K bps. The default port  
speed is 57.6K bps.  
72  
 
The Word Length option sets the number of bits in a word. The word  
length range is 5 to 8 bits. The default is 8 bits.  
The Stop Bits option sets the number of stop bits. The number of stop  
bits can be 1, 1.5, or 2. The default is 1 bit.  
The Parity option sets parity for odd, even or none. Under normal  
conditions, parity is set to none. The default is none.  
The Flow Control option allows for two types of flow control: the soft-  
ware-based XON/XOFF and the hardware-based Clear to Send (CTS).  
The default condition is CTS. Flow control is the means by which data  
flow from the device into the MultiFRAD is controlled. Flow control is  
necessary when the data handling capacity of the data port cannot keep  
up with the volume of data sent to it. When the data device controls data  
flow to itself, it is called pacing (see Pacing option). The combination of  
flow control from the port device and pacing to the data device is how  
data transfers are regulated so that no data is lost.  
CHANNEL DEVICE-  
INITIATED PACING  
MultiFRAD-INITIATED  
FLOW CONTROL  
DATA  
DATA  
Channel  
Device  
Channel  
Device  
MultiFRAD  
MultiFRAD  
Flow control stops the input  
of data to the MultiFRAD  
Pacing stops the output of  
data from the MultiFRAD  
The Enq/Ack Flow Control option is a special flow control protocol used  
in Hewlett Packard computer systems. This option is sometimes  
referred to as Enquire/Acknowledge flow control because it’s based on  
the computer sending an enquiry (ENQ) and then expecting an ac-  
knowledgment (ACK). The default condition for this option is off.  
The Echo option enables data entered on the data device keyboard to  
be returned to the device's monitor. The purpose of this option is so that  
an operator will not experience undue delays in seeing entered data  
appear on their monitor. The default condition for the echo option is off.  
The Pacing option controls the data flow to the data device. This option  
only applies to the async mode of operation. Pacing is necessary when  
the flow of data to a device operating on the data port is more than it can  
process. If the device cannot process the volume of data sent to it, then  
the pacing option should be turned on. The pacing method used is  
determined by the type of flow control. The default condition is for this  
option to be turned off.  
73  
 
The EIA Pass Through option allows the data device to receive EIA  
control signals through the MultiFRAD. This option only applies during  
the async mode of operation. Since, in normal interactive operation, the  
existence of a MultiFRAD should be transparent to the user, the EIA  
pass through option allows a terminal to operate as if it were connected  
directly to a communications line and not through a MultiFRAD. This is  
done by allowing selected pins (signals) on one MultiFRAD to be  
passed through to selected pins on a remote MultiFRAD. The default  
condition is for this option to be turned off. The following diagram shows  
how the EIA pass through option routes the selected signals:  
MultiFRAD  
B
MultiFRAD  
A
IN 4  
8 OUT  
6 OUT  
IN 20  
Trunk Facility  
OUT 8  
OUT 6  
4 IN  
20 IN  
The Pass Xon option enables the XON/XOFF flow control signals to be  
passed on to the data device. This option only applies during the async  
mode of operation. This option has to be used in conjunction with the  
software-based XON/XOFF flow control option. The default condition is  
for this option to be turned off, and normally it should remain off.  
74  
 
6.2.2 Sync Data Port Configuration  
The Sync Data Port Configuration menu allows you to configure the  
data port for either asynchronous or synchronous operation, depending  
on the type of device connected to the port.  
When the port is configured for synchronous operation, the following  
Data Port Configuration menu displays the default parameters:  
Data Port Configuration  
1 - Async/Sync:  
2 - Speed:  
Sync  
57600  
Flags  
NRZ  
All 1s  
Off  
3 - Idle Condition:  
4 - NRZ/NRZI Encoding:  
5 - CRC Preset:  
6 - Inter-frame Timer:  
S - Store All Configurations  
M - Main Menu  
P - Previous Menu  
Selection : _  
The Async/Sync option configures the port for either asynchronous or  
synchronous operation. When a synchronous device such as a LAN  
bridge or router is connected to the port, the data port needs to be  
configured for synchronous operation.  
The Speed option needs to be set to match the speed of the sync  
device. When the data port is connected to a synchronous device, the  
baud rate is from 300 bps up to 128K bps. The default channel speed is  
56K bps.  
The Idle Condition option must be set to match the idle condition of the  
synchronous device connected to the data port. The idle condition  
determines what happens when the synchronous data line is idle (i.e.,  
no data frames are being transmitted). The default condition is to  
continuously send SDLC flags (Flags). The other idle condition is the  
mark state (Mark). The transmit LED will be off during idle time if the  
synchronous device is in the mark state during idle conditions.  
The NRZ/NRZI Encoding option refers to the fact that synchronous data  
can be encoded by using either the NRZ (Non-Return to Zero) or NRZI  
(Non-Return to Zero Inverted) method. This option must match the  
synchronous device’s encoding. The default is NRZ. With NRZ encod-  
75  
 
ing, data is represented normally. With NRZI encoding, a logical one is  
represented by no transition and a zero is represented by a transition at  
the beginning of the bit. Most synchronous devices can be configured  
for either NRZ or NRZI. If a synchronous device is not configurable, it  
most likely is set to NRZ. Refer to the device’s user documentation for  
the encoding method.  
The CRC Preset option allows the user to specify whether the polyno-  
mial used to calculate the CRC for each frame is preset to all 1s or all  
0s. This option must match the synchronous device’s CRC-preset  
setting. The default is All 1s.  
The Inter-frame Timer option can be changed to make the MultiFRAD  
wait a specified length of time between frames being transmitted on the  
data port. The user can choose delay times of 2,5,10 and 15 millisec-  
onds. A typical use for this parameter is to simulate transmission delays  
encountered with equipment that toggles hardware signals after  
transmission of each frame, like PC cards used to connect to legacy  
systems. The following options can be specified for the timer: Off, 2mS,  
5mS, 10mS, and 15mS. The default is off.  
76  
 
6.2.3 Trunk Configuration  
The Trunk Configuration menu allows you to configure the trunk. The  
default parameters are displayed in the following menu:  
T r u n k C o n f i g u r a t i o n  
1
2
3
4
5
6
7
8
9
-
-
-
-
-
-
-
A c c e s s r a t e :  
R T S S i g n a l S t a t u s :  
B a c k t o B a c k :  
D L C I :  
5 6 0 0 0  
F o l l o w s i n p u t f r o m D T E  
O f f  
1 6  
C o m m i t t e d I n f o R a t e ( C I R ) : 3 2 K  
E x c e s s B u r s t R a t e ( B e ) :  
M a n a g e m e n t t y p e :  
P o l l i n g I n t e r v a l :  
2 4 K  
A n n e x  
A
-
-
1 0 S e c  
F u l l S t a t u s C o u n t e r :  
6
1 0 - E r r o r T h r e s h o l d :  
3
11 - M o n i t o r e d E v e n t C o u n t :  
1 2 - E n c a p s u l a t i o n M o d e :  
4
M u x  
S
M
P
-
S t o r e A l l C o n f i g u r a t i o n s  
M a i n M e n u  
-
-
P r e v i o u s M e n u  
S e l e c t i o n  
:
_
The Access Rate option displays the maximum data rate of the trunk.  
The Access Rate determines the speed of the access channel (trunk).  
The Access Rate can not be changed.  
The RTS (Request-To-Send) Signal Status of Follows input from DTE  
enables the DTE to control the carrier on status on the trunk. The RTS  
Forced ON option is used in the DSU-only mode when a multi-drop  
application is used and is only used by the host unit. The default is  
Follows input from DTE.  
The Back to Back option is used to test the port by connecting two  
MultiFRADs together without a frame relay network in between them.  
Back-to-back mode still requires the use of DSU/CSUs, but they should  
not be connected over the frame relay network. The options are On and  
Off with a default of Off.  
Back-to-back mode is useful when two MultiFRADs are at the same  
location and they are connected via DSUs for testing. Back-to-back mode  
can also be used to connect two MultiFRADs over a private leased line.  
The DLCI option (Data Link Connection Identifier) is assigned by the frame  
relay service provider for the PVC (Permanent Virtual Circuit) that is on your  
77  
 
access circuit. Set the DLCI to indicate the PVC to terminate the trunk. The  
range of DLCIs is from 16 to 1007 with a default of 16.  
The Committed Info Rate (CIR) option determines the data transfer rate  
at which the network is committed to handle under normal conditions.  
This rate is the average over a minimum increment of time. The CIR  
may be less than or equal to the Access Rate. When the CIR is ex-  
ceeded, but the data rate is below the Excess Burst Rate (Be), there is a  
possibility that data may be discarded. When the Be is exceeded, data  
will most likely be discarded. The default CIR is 32K.  
The Excess Burst Rate (Be) option defines the maximum allowable  
data transfer rate the MultiFRAD can exceed the Committed Info Rate  
(CIR) during a time interval. The Be is the maximum additional data rate  
at which the MultiFRAD can present to the network during a time  
interval. The default Be is 24K.  
The Management Type option defines a set of procedures and mes-  
sages to manage PVCs and the physical link at the user network  
interface. Three management types are used: Local Management  
Interface (LMI), Annex A, Annex D. The management type is determined  
by the network at subscription time.  
The Polling Interval option defines a time period (T391) in which a Status  
Enquiry message is sent from the MultiFRAD to the network. The Status  
Enquiry message requests the status of the PVC(s) or verification of the  
status of a physical link. When the Status Enquiry message is sent by the  
MultiFRAD, the Polling Interval is restarted. The network responds with a  
status message that reports the status of the PVC or verifies the integrity of  
the physical link. The polling interval is 5 to 30 seconds with a default of 10  
seconds.  
The Full Status Counter option determines how many Polling Intervals take  
place before a full status (N391) is sent from the network. A Full Status  
Enquiry message is sent from the MultiFRAD to the network requesting  
status reports of all the PVCs on the physical link.  
The Error Threshold Count option is used to indicate the threshold  
number of errors occurring during a full cycle of the Monitored Event  
Counter. After each full cycle of the Monitored Event Counter, if the  
actual number of errors equals or exceeds the error threshold, the trunk  
status is brought down and no data may be sent. The error count is  
reset at the beginning of each cycle of the Monitored Event Counter. The  
Error Threshold Count can range from 1 to 10 with a default of 3 and  
78  
 
should be less than or equal to the Monitored Event Counter.  
The Monitored Event Counter option determines the number of Polling  
Intervals that have to take place before the User Network Interface is  
operational. It is also used with the error threshold count to determine if  
the trunk should be brought down. The range of this counter is from 1 to  
10 events with a default of 4 events.  
The Encapsulation Mode option depends on the type of device that is  
connected at the other end of the trunk. If another MultiFRAD 100 is  
connected at the other end of the trunk, then the Mux mode is used. If a  
non-MultiFRAD 100 is at the other end of the trunk, then the Raw mode  
is used.  
79  
 
6.3  
Statistics  
The Statistics menu allows you to view or clear statistics, or return to the  
previous menu or to the Main Menu.  
Statistics  
1 - View Statistics  
2 - Clear Statistics  
M - Main Menu  
P - Previous Menu  
Selection : _  
To view or clear statistics, enter the corresponding option number and  
press ENTER. To return to the previous menu, enter P and press ENTER.  
To return to the Main Menu, enter M and press ENTER.  
Two Trunk Statistics Menus are provided depending on how the data  
channel is configured. If the data channel is configured for an asynchro-  
nous mode of operation, then the Async Data Frames Retransmitted and  
Link Alarms statistics are presented. If the data channel is configured  
for synchronous mode of operation, then the Async Data Frames  
Retransmitted and Link Alarms statistics are not presented. The Trunk  
Statistics Menus provide information concerning the operation of the  
MultiFRAD that can aid you in testing for problems.  
Trunk Statistics  
Elapsed Time  
:
:
:
:
:
00 Days 06 Hours 59 Minutes  
Data Frames Transmitted  
Data Frames Received  
Receive Errors  
0
0
0
0
Remote Downs  
Async -  
Data Frames Retransmitted  
Link Alarms  
:
:
:
:
0
0
0
0
0
0
0
Status Enquiries Transmitted  
Status Messages Received  
Full Status Messages Received :  
Async Status Messages Received :  
Bad Status Messages Received  
:
In Async mode, comparing the number of frames transmitted with the  
number of retransmits needed to get data over the link can indicate a  
line problem. Comparing the data frames received and receive errors  
can also indicate a problem with the trunk. Comparative numbers that  
80  
 
you might encounter could be 10,000 frames transmitted (or received)  
with 500 or 1000 retransmits (or receive errors). Link alarms simply tell  
you that there is some sort of problem on the trunk in async mode. You  
will find that the link alarms number will correspond to the retransmit  
and received frames numbers. Specifically, a link alarm means that it  
has been 10 seconds since the MultiFRAD has received an acknowl-  
edgment. Normally, three acknowledgments are received during a 10-  
second period.  
The Remote Downs entry means that the MultiFRAD has sent data 30  
times and could not get it through (the link between the two MultiFRADs  
is broken).  
The Status Enquiries Transmitted count shows how many enquiries  
the MultiFRAD has sent to the network. An enquiry is sent every time  
the Polling Interval Timer expires (default of 10 seconds).  
There are 4-counts of status messages received from the network.  
Status messages are sent by the network in response to the status  
enquiries from the MultiFRAD. The sum of the status messages re-  
ceived count and the full status messages received count should equal  
the status Enquiry Transmitted count.  
The Status Messages Received count indicates the number of Keep-  
Alive status messages the network has sent.  
The Full Status Messages Received count indicates the number of Full  
Status Messages (messages that include the PVC status - either new or  
active) received in response to a status enquiry.  
The Async Status Messages Received count indicates the number of  
PVC status messages that were received independently, not as a  
response to an enquiry from the MultiFRAD.  
The Bad Status Messages Received count indicates the number of  
status messages received that were bad due to a frame-level error (a  
bad CRC or an aborted frame) or a protocol error (due to the wrong  
management type, etc.)  
81  
 
6.4  
Reset Options  
The Reset Options menu allows you to reset the unit, the data channel,  
or return to the previous menu or to the Main Menu.  
Reset Options  
1 - Reset Unit  
2 - Reset Data Channel  
M - Main Menu  
P - Previous Menu  
Selection : _  
To reset the unit, enter 1 and press ENTER. To reset the data channel,  
enter 2 and press ENTER. To return to the previous menu, enter P and  
press ENTER. To return to the Main Menu, enter M and press ENTER.  
6.5 Diagnostic Tests  
The Diagnostic menu allows you to run two loopback tests, a watch dog  
test, display the product and firmware identification or return to the  
previous menu or the Main Menu.  
Diagnostics  
1 - Loop Tests  
2 - Memory Tests  
3 - Watch Dog Test  
4 - Product and Firmware ID  
5 - Flash Firmware Upgrade  
M - Main Menu  
P - Previous Menu  
Selection : _  
6.5.1 Loop Tests  
The Loop Tests menu allows for selection of two loopback tests, or  
return to the previous menu or to the Main Menu. The Data Port Loop-  
back Test tests the interface between the data device and the Multi-  
FRAD. The Trunk Loopback Test tests can be used both locally and  
remotely. When it is used locally, the internal DSU should be set to  
82  
 
loopback mode (DIP-Switch 3 DOWN). This tests the complete path  
through the MultiFRAD up to the line circuitry and back to the data port.  
When it is used in a remote trunk loopback test mode, the remote DSU  
(or the telephone company's central office, CO) would be put into  
loopback mode. This tests the integrity of the local data device, Multi-  
FRAD, and the frame relay network. The Remote Trunk Loopback test is  
the most sophisticated of the two tests.  
Loop Tests  
1 - Data Port Loopback  
2 - Trunk Loopback  
M - Main Menu  
P - Previous Menu  
Selection : _  
The Data Port Loopback Test puts the MultiFRAD's data port in  
loopback mode. This means that any data that comes into the data port  
is immediately looped back out to the user device. Use this test to verify  
that the data port cable and its connections are OK, and that the  
MultiFRAD's data port settings are correct.  
The Trunk Loopback Test is selected when the internal DSU is set for  
loopback mode (DIP-Switch 3 is DOWN). This tests the data port  
circuitry and the MultiFRAD's trunk circuitry up the DDS line circuit.  
The methodology for all of the tests is the same:  
1. Put the MultiFRAD (either the local or remote one) into the desired  
test mode.  
2. Connect the user device to the data port of the local MultiFRAD.  
3. Send data from the user device.  
4. Verify that the data received from the MultiFRAD matches exactly  
what was sent.  
5. If the data received is the same as the data sent, then the test  
passed. If the data received is corrupted or no data is received,  
then the test failed. A failed test indicates a problem either with  
the cables, connections, or one of the units involved in the test. If  
the cause of the failure is not readily apparent, try using the  
process of elimination to isolate the trouble spot(s). The tests are  
listed in order of complexity. If the Remote Trunk Loopback fails,  
83  
 
try going back to the Local Trunk Loopback, and then even the  
data port loopback which is the most basic test. If there is still no  
clear cause of the problem, follow the steps in section 7.3,  
contacting Tech support.  
6.5.2 Memory Test  
The memory test verifies that each memory chip on the circuit board is  
working. The memory test destroys all stored parameters.  
6.5.3 Watch Dog Test  
The watch dog is a special circuit designed to reset the unit in case of a  
catastrophic error in the firmware. The watch dog test verifies that the  
watch dog circuitry is working.  
6.5.4 Product and Firmware ID  
This option displays the product identification and firmware version  
number.  
6.5.5 Flash Firmware Upgrade  
The flash firmware upgrade option is used to upgrade the firmware  
code in the PROM. Refer to Chapter 7, section on upgrading the flash  
PROM for detailed procedures.  
84  
 
7
Service, Warranty  
and Tech Support  
 
86  
 
7.1  
Introduction  
This chapter begins with your MultiFRAD 100-Series 2-year warranty.  
Read carefully the next section, “Tech Support,” if you have questions  
about or problems with your MultiFRAD. It includes the technical support  
telephone numbers, space for recording your product information, and  
an explanation of how to send in your MultiFRAD should you require  
service. The final three sections explain how to use our bulletin board  
service (BBS), and get support through CompuServe and the Internet.  
7.2  
Limited Warranty  
Multi-Tech Systems, Inc. (“MTS”) warrants that its products will be free  
from defects in material or workmanship for a period of two years from  
the date of purchase, or if proof of purchase is not provided, two years  
from date of shipment. MTS MAKES NO OTHER WARRANTY, EX-  
PRESSED OR IMPLIED, AND ALL IMPLIED WARRANTIES OF MER-  
CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE  
HEREBY DISCLAIMED. This warranty does not apply to any products  
which have been damaged by lightning storms, water, or power surges  
or which have been neglected, altered, abused, used for a purpose  
other than the one for which they were manufactured, repaired by the  
customer or any party without MTS’s written authorization, or used in  
any manner inconsistent with MTS’s instructions.  
MTS’s entire obligation under this warranty shall be limited (at MTS’s  
option) to repair or replacement of any products which prove to be  
defective within the warranty period, or, at MTS’s option, issuance of a  
refund of the purchase price. Defective products must be returned by  
Customer to MTS’s factory transportation prepaid.  
MTS WILL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES AND  
UNDER NO CIRCUMSTANCES WILL ITS LIABILITY EXCEED THE PUR-  
CHASE PRICE FOR DEFECTIVE PRODUCTS.  
7.3  
Tech Support  
Multi-Tech has an excellent staff of technical support personnel avail-  
able to help you get the most out of your Multi-Tech product. If you have  
any questions about the operation of this unit, call 1-800-972-2439.  
Please fill out the MultiFRAD information form below and have it  
available when you call. If your MultiFRAD requires service, the tech  
support specialist will guide you on how to send it in (see section 7.3.2).  
87  
 
7.3.1 Recording MultiFRAD Information  
Please fill in the following information on your Multi-Tech MultiFRAD.  
This will help Tech Support in answering your questions. (The same  
information is requested on the Warranty Registration Card.)  
Model Number: ______________________________________  
Serial Number: ______________________________________  
Firmware Version: ____________________________________  
The model and serial numbers are on the bottom of your MultiFRAD.  
The Diagnostics menu displays the PROM firmware version number.  
Before calling Tech Support, please note in the space below if your  
MultiFRAD is connected to a synchronous or asynchronous device on  
the data port. Also note status information about your MultiFRAD,  
including LED indicators, screen messages, diagnostic test results, or  
problems with a specific application, etc.  
_________________________________________________________________________________  
_________________________________________________________________________________  
_______________________________________________________________________________  
________________________________________________________________________________________________________  
______________________________________________________________________________________________________________  
_______________________________________________________________________________________________________  
___________________________________________________________________________________________________________________  
_________________________________________________________________________________________________________________________  
___________________________________________________________________________________________________________________  
_________________________________________________________________________________________________________________________  
___________________________________________________________________________________________________________________  
_________________________________________________________________________________________________________________________  
88  
 
7.3.2 Service  
If your tech support specialist decides that service is required, your  
MultiFRAD may be sent (freight prepaid) to our factory. Return shipping  
charges will be paid by Multi-Tech Systems.  
Include the following with your MultiFRAD:  
• A description of the problem.  
• Return billing and shipping addresses.  
• Contact name and phone number.  
• Check or purchase order number for payment if the MultiFRAD is  
out of warranty. (Check with your technical support specialist for the  
standard repair charge for your MultiFRAD).  
• If possible, note the name of the technical support specialist with  
whom you spoke.  
If you need to inquire about the status of the returned product, be prepared  
to provide the serial number of the product sent (see section 7.3.1).  
Send your MultiFRAD to this address:  
MULTI-TECH SYSTEMS, INC.  
2205 WOODALE DRIVE  
MOUNDS VIEW, MINNESOTA 55112  
ATTN: SERVICE OR REPAIRS  
You should also check with the supplier of your MultiFRAD on the availabil-  
ity of local service and/or loaner units in your part of the country.  
7.4  
About the Multi-Tech BBS  
Multi-Tech Systems maintains a Bulletin Board Service (BBS) for its  
customers. The information available via the BBS includes new product  
information, product upgrade data, problem-solving tips, and a mes-  
sage service you can use to obtain additional information about Multi-  
Tech products, including the ones you own. The phone number for the  
Multi-Tech BBS is (612) 785-3702 or (800) 392-2432 (U.S.A. and  
Canada).  
The BBS can be accessed by any asynchronous modem operating at  
1200 bps to 33,600 bps at a setting of 8 bits, no parity, and 1 stop bit (8-  
N-1).  
89  
 
7.4.1 Logging on to the Multi-Tech BBS  
To log on to the Multi-Tech BBS, perform the following steps.  
1. Set your communications program to 8-N-1.  
2. Dial our BBS at (800) 392-2432 (USA and Canada) or (612) 785-  
3702 (international and local).  
3. At the prompts, type your first name, last name, and password; then  
press ENTER. If you are a first time caller, the BBS will ask if your  
name is spelled correctly. If you answer yes, a questionnaire will  
appear. You must complete the questionnaire to use the BBS on your  
first call.  
4. Press ENTER until the Main Menu appears. From the Main Menu  
you have access to three main areas: the Files Menu, the Message  
Menu, and Bulletins. For help on menu commands, type ?.  
7.4.2 Downloading a File  
If you know the file name  
1. From the Main Menu, type F to access the Files Menu, then type D.  
2. Enter the name of the file you wish to download from the BBS.  
3. If a password is required, enter the password.  
4. Answer Y or N to the automatic logoff question.  
5. Select a file transfer protocol by typing the indicated letter, such as Z  
for Zmodem (the recommended protocol).  
6. If you select Zmodem, the transfer will begin automatically. If you  
select another protocol, you may have to initiate the transfer  
yourself. (In most datacomm programs, the PAGE DOWN key  
initiates the download.)  
7. When the download is complete, press ENTER to return to the File  
Menu.  
8. To exit the BBS, type G and press ENTER.  
90  
 
If you don’t know the file name  
1. From the Main Menu, type F to access the Files Menu. For a list of file  
areas, type L, press ENTER, then type L and press ENTER again. (If  
you do not type the second L, you will list all of the files on the BBS.)  
2. Mark each file area you would like to examine by typing its list  
number and pressing ENTER.  
3. Enter L to list all the files in the selected file areas. Enter C to go  
forward in the file list and P to go back.  
4. To mark one or more files for download, type M, press ENTER, type  
the list numbers of the files, and press ENTER again.  
5. Enter D. You will see a list of the files you have marked. Enter E if you  
would like to edit the list; otherwise enter D again to start the  
download process.  
6. Select a file transfer protocol by typing the indicated letter, such as Z  
for Zmodem (the recommended protocol).  
7. If you select Zmodem, the file will transfer automatically. If you select  
another protocol, you may have to initiate the transfer yourself. (In  
most data communications programs, the PAGE DOWN key initiates  
the download.)  
8. When the download is complete, press ENTER to return to the File  
Menu.  
9. To exit the BBS, type G and press ENTER.  
7.5  
About CompuServe  
In addition to the BBS, Multi-Tech provides support through  
CompuServe’s Modem Vendor Forum (GO MODEMVEN). Refer to your  
CompuServe documentation for special operating procedures.  
91  
 
7.6  
About the Internet  
Multi-Tech is a commercial user on the Internet, and we retrieve  
messages from our customers on a periodic basis. Multi-Tech’s pres-  
ence includes a Web site at:  
and an ftp site at:  
Multi-Tech's presence includes a Web site at:  
7.7  
About the Multi-Tech Fax-Back Service  
Multi-Tech’s fax-back system provides 24-hour access to sales, market-  
ing, and technical literature. Dial 612-717-5888, follow the voice  
prompts, and request document number 10 for a catalog of available  
documents. For convenience, have your fax number handy:  
_________________________. From the catalog of available docu-  
ments, you can order newsletters, white papers, press releases, etc.  
from the sales and marketing index (pages 1-4), or order basic modem  
operation and troubleshooting guides from the technical support and  
engineering index. Just enter the applicable FB Doc. # from the left  
column of the catalog.  
92  
 
7.8  
Upgrading the Flash PROM  
Your MultiFRAD has a Flash PROM which contains firmware code for  
the hardware. At various times, Multi-Tech may add enhancements and/  
or fixes to the firmware. The Flash technology used in your MultiFRAD  
allows these upgrades to be loaded directly into the PROM chip through  
the serial port.  
7.8.1 Using FlashPro to Upgrade MultiFRAD Firmware  
1. Download FLASHPRO.ZIP and a new .HEX file from the Multi-Tech  
BBS.  
2. Unzip the FLASHPRO.ZIP file. Place this unzipped file and the .HEX  
file in the same directory.  
3. Run FlashPro by typing FLASHPRO and hitting ENTER at the DOS  
prompt.  
4. Highlight the "Configure" option in the MAIN MENU and hit ENTER.  
Highlight "Active Port" and select the COM port to which you have  
your MultiFRAD attached. Highlight "Baud Rate" and select the rate  
at which you want to program. Hit ESC when finished.  
5. Highlight the "Select File to Program" option in the MAIN MENU.  
Highlight the .HEX file. Hit ESC when finished.  
6. Highlight "Program Firmware" option in the MAIN MENU. When you  
are prompted to confirm the file to program, press "Y".  
7. If you have not successfully programmed FlashPro, return to step 3.  
To call Multi-Tech's Technical Support or BBS, refer to section 7.4.  
93  
 
94  
 
Appendices  
 
96  
 
Appendix A  
Cabling Diagrams  
Data Cables  
13 12 11 10  
9
8
7
6
5
4
3
2
1
25 24  
23 22  
21 20 19 18 17  
16 15 14  
Data connector  
RS232C/V.24 * Cable  
PIN NO.  
PIN NO.  
1
1
CHASSIS GROUND (AA)  
TRANSMIT DATA (BA)  
RECEIVE DATA (BB)  
2
2
3
3
4
4
REQUEST TO SEND (CA)  
CLEAR TO SEND (CB)  
SIGNAL GROUND (AB)  
CARRIER DETECT (CF)  
TRANSMIT CLOCK (DB)  
RECEIVE CLOCK (DD)  
DATA TERMINAL READY (CD)  
To Data  
To FR111  
Data Connector  
5
5
Device  
7
7
Connector  
8
8
15  
17  
20  
25  
15  
17  
20  
25  
V.35 Adapter Cable**  
V.35 34-PIN  
CONNECTOR (MALE)  
25-PIN  
CONNECTOR (FEMALE)  
A
B
C
D
E
F
1
PROTECTIVE GROUND  
SIGNAL GROUND  
7
4
REQUEST TO SEND  
CLEAR TO SEND  
5
6
DATA SET READY  
8
DATA CARRIER DETECT  
DATA TERMINAL READY  
TRANSMIT DATA A  
RECEIVE DATA A  
H
P
R
S
T
20  
2
3
12  
22  
23  
17  
25  
18  
15  
21  
TRANSMIT DATA B  
RECEIVE DATA B  
U
V
W
X
Y
a
EXTERNAL TX CLOCK A  
RECEIVE CLOCK A  
EXTERNAL TX CLOCK B  
RECEIVE CLOCK B  
TRANSMIT CLOCK A  
TRANSMIT CLOCK B  
* The FR111 RS232C interface circuits have been designed to meet the electrical  
specifications given in EIA (Electronic Industries Association RS232C and CCITT  
(Consultative Committee International Telegraph and Telephone) V.24 Standards.  
** When configured for V.35 interface operation, the V.35 adapter cable should be  
used. This cable uses a 25-pin female connector at one end and a 34-pin  
Winchester male connector at the other end.  
97  
 
Trunk Cable  
RT  
RR  
RT  
RR  
Receive  
{
Transmit  
{
1 2 3 4 5 6 7 8  
RJ-48 Cable  
Pin Identification  
Pin  
Description  
Destination  
1
2
3
4
5
6
7
8
Transmit Pair  
Transmit Pair  
N/C  
N/C  
N/C  
N/C  
Receive Pair  
Receive Pair  
To Line  
To Line  
From Line  
From Line  
98  
 
Back-To-Back Cable  
8
7
6
5
4
3
2
1
1
2
3
4
RJ48S  
RJ48S  
5
6
7
8
1
8
99  
 

Murray Lawn Mower 425604x18A User Manual
NCR Wireless Office Headset 5953 User Manual
NETGEAR Switch JFS516 User Manual
Nextar MP3 Player MA206 User Manual
Nokia Cell Phone 1202 User Manual
NordicTrack Home Gym 831237650 User Manual
Onkyo Stereo Receiver TX SR578 User Manual
Palsonic Stereo System PMSL 329 User Manual
Panasonic Answering Machine KX TC1731B User Manual
Paradyne Network Card MUM200 2 User Manual